05/10 AWA1230-2460
Vertical adapters 800/1600A on fixed
IZM low voltage circuit breakers
(1) Only qualified electrical persOnnel shOuld
be permitted tO wOrk On the equipment.
(2) always de-energize primary and
secOndary circuits if a circuit breaker
cannOt be remOved tO a safe wOrk lOcatiOn.
(3) all circuit breakers shOuld be switched
tO the Off pOsitiOn and mechanism springs
discharged.
failure tO fOllOw these steps fOr all
prOcedures described in this instructiOn
leaflet cOuld result in death, bOdily injury,
Or prOperty damage.
the instructiOns cOntained in this awa and On
prOduct labels have tO be fOllOwed. Observe
the five safety rules:
– discOnnecting
– ensure that devices cannOt be
accidentally restarted
– verify isOlatiOn frOm the supply
– earthing and shOrt-circuiting
– cOvering Or prOviding barriers tO
adjacent live parts
discOnnect the equipment frOm the supply.
use Only authOrized spare parts in the repair
Of the equipment. the specified maintenance
intervals as well as the instructiOns fOr
repair and exchange must be strictly adhered
tO prevent injury tO persOnnel and damage tO
the switchbOard.
Effective May 2010
 warning
 warning
2C14990H02
Section 1: General information
The vertical adapter bolts directly to the rear
primary terminal pads. This adapter will
not accommodate cable adapters, only bus
connections. A three-pole breaker will use a set
of six adapters (eight for four-pole). All required
mounting hardware is provided. Torque all bolts
to 37–43 ft-lbs (50–58 Nm).
Section 2: Installation of
vertical adapters
To install the vertical adapters, proceed with the
following two steps:
Step 1: Assemble as shown with the hardware
provided. Assembly to a load conductor is
demonstrated.
Load
Conductor
Flat Washer
M10 Hex Nut
Figure 1. Step 1
M10 x 45
Hex Bolt
Conical Spring
Washer
Flat Washer
Vertical Adapter

Advertisement

loading
Need help?

Need help?

Do you have a question about the 800A and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton 800A

  • Page 1 05/10 AWA1230-2460 Effective May 2010 2C14990H02 Vertical adapters 800/1600A on fixed IZM low voltage circuit breakers Section 1: General information  warning The vertical adapter bolts directly to the rear (1) Only qualified electrical persOnnel shOuld primary terminal pads. This adapter will be permitted tO wOrk On the equipment.
  • Page 2 Mount on Top of Line Conductor Mount on Bottom of Load Conductor Figure 2. Step 2 Eaton Industries GmbH Electrical Sector ©2010 by Eaton Industries GmbH Änderungen vorbehalten Subject to alterations 05/10 AWA1230-2460 / Z8694 Moon/Doku/Heng Printed in USA (05/10)
  • Page 3 05/10 AWA1230-2460 Gültig ab Mai 2010 2C14990H02 Vertikale Anschlüsse für 800/1600A Festeinbauschalter IZM-TV… Abschnitt 1: Allgemeine  Warnung Informationen (1) nur qualifiziertes Personal mit elektrotechnischer ausbildung sollte die Die vertikalen Anschlüsse werden direkt mit erlaubnis erhalten, an dem gerät zu arbeiten. den Horizontalanschlüssen verschraubt.
  • Page 4 Einspeiseseite: Montage der Adapter oberhalb der Anschlussleiste Abgangsseite: Montage der Adapter unterhalb der Anschlussleiste Abbildung 2. Schritt 2 Eaton Industries GmbH Electrical Sector ©2010 by Eaton Industries GmbH Änderungen vorbehalten Subject to alterations 05/10 AWA1230-2460 / Z8694 Moon/Doku/Heng Printed in USA (05/10)

This manual is also suitable for:

1600a