Equivalent Area Of Masonry Chimney Liners; Inspection Of Tile−Lined Masonry Chimney - Lennox 18M7901 Installation Instructions Manual

Masonry chimney vent adapter
Table of Contents

Advertisement

Nominal Liner Size
(inches X inches)
4 X 8
8 X 8
8 X12
12 X12
12 X 16
16 X 16
16 X 20
20 X 20
Inspection of Tile−Lined Masonry Chimney
The chimney must be inspected and found to be in good
condition. Chimney construction must conform with the
National Fuel Gas Code NFPA 54/ANSI Z223.1, Standard
for Chimneys, Fireplaces, Vents and Solid−Fuel−Burning
Appliances ANSI/NFPA 211, and to any applicable state
or local codes.
The following conditions must be confirmed before
continuing with installation of the vent system:
D Chimney must be lined with clay tile.
D Chimney crown must be in good condition. Missing
mortar or brick must be replaced.
D Tile liner and top seal must be in good condition. If
necessary, make repairs.
D All debris (mortar, tile, fuel oil residue, etc.) must be
removed from chimney clean out.
D Tile liner must be inspected to make sure that tiles
are properly aligned, that all sections are complete
and that there are no gaps. If necessary, make
repairs.
D Exterior chimneys must serve at least one other
drafthood−equipped
continuing.

Equivalent Area of Masonry Chimney Liners

Inside Liner
Dimensions
(inches)
2−1/2 X 6−1/2
6−3/4 X 6−3/4
6−1/2 X 10−1/2
9−3/4 X 9−3/4
9−1/2 X 13−1/2
13−1/4 X 13−1/4
13 X 17
16−1/2 X 16−3/4
appliance.
Verify
before
TABLE 6
Inside Diameter or
Equivalent Diameter
(inches)
4
5
6
7
7.4
8
9
10
10.4
11
11.8
12
14
14.5
15
16.2
18
18.2
20
D Chimney must be properly sized per these
instructions.
Installation
1 − Turn off all gas supply and electrical power to unit.
These instructions must be followed exactly. This
kit must be installed by a qualified service techni-
cian. Improper installation may result in personal
injury, loss of life, equipment damage, or damage to
the existing masonry chimney.
2 − A 7/8" diameter hole is required to accommodate
the conduit for the wiring from the blocked vent
switch in the vent adapter to the pressure switch in
the furnace. A template is provided to ensure proper
location of the hole in the unit top cap.
The conduit hole must be positioned carefully to
avoid contact between the blocked vent switch
wiring and the combustion air inducer or hot
surfaces inside the furnace.
Page 6
Equivalent Area
(square inches)
12.2
19.6
28.3
38.3
42.7
50.3
63.6
78.5
83.3
95
107.5
113
153.9
162.9
176.7
206.1
254.4
260.2
314.1
WARNING