Lennox ELITE Series Installation Instructions Manual page 54

Upflow / horizontal air discharge
Table of Contents

Advertisement

ADDENDUM FOR ALL PROVINCES OF CANADA
See below for venting in all provinces of Canada. Lennox approves the following termination for use in all provinces of
Canada.
B − Horizontal separation between
C − Exhaust pipe length
NOTE − Flue gas may be acidic and may adversely affect some building materials. If flue gases impinge
on the building materials, a corrosion−resistant shield should be used to protect the wall surface. The
shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks,
etc. in affected area, should be sealed using an appropriate sealant.
A − Clearance above grade or
average snow accumulation
intake and exhaust
D − Wall support distance from top
of each pipe (intake/exhaust)
C
D
B
12"
A
2" (51MM)
Vent Pipe
12" (305 mm) Min. 12" (305 mm) Min.
6" (152 mm) Min.
6" (152 mm) Min.
24" (610 mm) Max.
24" (610 mm) Max.
Per: Saskatchewan Code of Practice
6" (152 mm) Max.
Page 54
3" (76MM)
Vent Pipe
6" (152 mm) Max.