3.1. Digital Outputs [-EB1]

3.1. Digital Outputs [-EB1]
Optically-isolated solid-state relays drive the digital outputs. You can connect the digital outputs in
current sourcing or current sinking mode but you must connect all four outputs in a port in the same
configuration. Refer to
The digital outputs are not designed for high-voltage isolation applications and they should only be used
with ground-referenced circuits.
You must install suppression diodes on digital outputs that drive relays or other inductive devices. To see
an example of a current sourcing output that has diode suppression, refer to
example of a current sinking output that has diode suppression, refer to
The digital outputs have overload protection. They will resume normal operation when the overload is
removed.
Table 3-1:
Digital Output Specifications [-EB1]
Digital Output Specifications
Maximum Voltage
Maximum Sink/Source Current
Output Saturation Voltage
Output Resistance
Rise / Fall Time
Reset State
90
Figure 3-3
and
Figure
3-4.
Figure
Figure 3-4
Value
24 V (26 V Maximum)
250 mA/output
0.9 V at maximum current
3.7 Ω
250 µs (2K pull up to 24V)
Output Off (High Impedance State)