Troubleshooting

If the fans are not running or do not perform pro-
perly, check the following:
• The functions and settings of the built-in
control system.
• That the intake grille/filter is not dirty.
If there is no heat, check the following:
• The functions, internal sensor and settings of
the built-in control system.
For units with electrical heating, also check the
following:
• Power supply to electric heater coil; check
fuses and circuit-breaker (if any).
• That the overheat protection has not been
deployed.
For units with a water coil, also check the follo-
wing:
• That the water coil is air free.
• That there is sufficient water flow and
pressure.
• That incoming water is heated adequately.
If the fault cannot be rectified, please contact a
qualified service technician.
Residual current circuit breaker (E)
When the installation is protected by means of
a residual current circuit breaker, which trips
when the appliance is connected, this may be
due to moisture in the heating element. When
an appliance containing a heater element has
not been used for a long period or stored in
a damp environment, moisture can enter the
element.
This should not be seen as a fault, but is
simply rectified by connecting the appliance to
the main supply via a socket without a safety
cut-out so that the moisture can be eliminated
from the element. The drying time can vary
from a few hours to a few days. As a preventive
measure, the unit should occasionally be run
for a short time when it is not being used for
extended periods of time.
Packaging
Packaging materials are chosen with
consideration to the environment and are
therefore recyclable.
20
AREC3200C
Handling of product at end of working
life
This product may contain substances necessary
for the functionality of the product but
potentially dangerous for the environment. The
product should not be disposed of mixed with
general household waste but delivered to a
designated collection point for environmental
recycling. Please contact the local authority
for further details of your nearest designated
collection point.
Safety
• For all installations of electrically heated
products a residual current circuit breaker 300
mA for fire protection should be used.
• Keep the areas around the air intake and
exhaust grilles free from possible obstructions!
• The unit must not be fully or partially covered as
overheating can result in a fire risk!
• Lifting equipment must be used to lift the unit.
• This appliance can be used by children aged
from 8 years and above and persons with
reduced physical, sensory or mental capabilities
or lack of experience and knowledge if they
have been given supervision or instruction
concerning use of the appliance in a safe way
and understand the hazards involved. Children
shall not play with the appliance. Cleaning and
user maintenance shall not be made by children
without supervision.
• Children of less than 3 years should be kept
away unless continuously supervised.
• Children aged from 3 years and less than 8
years shall only switch on/off the appliance
provided that it has been placed or installed
in its intended normal operating position and
they have been given supervision or instruction
concerning use of the appliance in a safe way
and understand the hazards involved.
• Children aged from 3 years and less than 8
years shall not plug in, regulate and clean the
appliance or perform user maintenance.
CAUTION — Some parts of this product can
become very hot and cause burns. Particular
attention has to be given where children and
vulnerable people are present.