Audio signal interface
Hide thumbs Also See for QIF-2011:

Advertisement

Quick Links

QIF-2011 audio signal interface installation manual
The QIF-2011 allows external audio signals to be sent over the paging channel of the
QX-5000.
Up to four different external signals can be connected to the QIF-2011, each with an
individual level adjustment. Signal 1 has highest priority, signal 4 the lowest. Jumpers
allow setting the priority of the signals over QX-5000 native paging or alarm signals.
Signal inputs 3 and 4 have built-in attenuators to allow direct connection of 70VRMS or
25VRMS signal lines to the interface.
The external signals are activated through a dry contact closure. If needed, both the audio
and the control inputs wiring can be supervised for faults by setting the appropriate
jumper. When supervision is required, 3.9K Ohms end of line resistors must be connected
to each control and audio signal lines.
Outputs are provided to control which zones are selected for paging. Each signal can
control a specific number of zones as programmed using the QX-5000 audio configurator
(this requires a QIF-2000 input extender to be installed in the QX-5000). For simpler
systems, a common output is provided for direct interface to one of the QIF-5000 opto-
coupled inputs.
A dry contact is provided for strobe controls. It will close if either external signals or
QIF-5000 paging are active.
Shielded pairs should be used for all audio signals. The interface should be installed next
to or inside the QX-5000 enclosure.
LT-6041 Rev 3

Advertisement

loading
Need help?

Need help?

Do you have a question about the QIF-2011 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Mircom QIF-2011

  • Page 1 QIF-2011 audio signal interface installation manual The QIF-2011 allows external audio signals to be sent over the paging channel of the QX-5000. Up to four different external signals can be connected to the QIF-2011, each with an individual level adjustment. Signal 1 has highest priority, signal 4 the lowest. Jumpers allow setting the priority of the signals over QX-5000 native paging or alarm signals.
  • Page 2 FIGURE 1: QIF-2011 INTERFACE CONTROLS AND INDICATORS ( Note: On early boards , QM and VT terminals were identified as QP and VO and first hi-voltage input belonged to zone 3 instead of zone2) Terminal identification table Terminal Function SH (beside R1)
  • Page 3 Return for MP (QIF-5000 J4 screws 8 or 6 depending on control internal connection)) signal used). Connection for Push-to-Talk line from QMP-510X series remote paging microphone consoles (QMP-510X terminal PTT IN +) . Provides QX-5000 internal paging status to the QIF-2011 interface LT-6041 Rev 3...
  • Page 4 Terminal Function Return for AP signal. Connects to QMP-510X terminal PTT IN - Connects to push to talk input on QIF-5000 (J2 terminal 1). This input is used to activate paging function of the QX-5000 system. Return for QP signal. Connect to QIF-5000 J2 terminal 2. Across PC terminals Paging active dry contact.
  • Page 5 Figure 2: X1 TO X4 JUMPERS CONFIGURATION (WITH BOARD VIEWED AS IN FIGURE 1) LEDs and potentiometers identification tables LEDs , POTs Function Green led indicating that interface is operational Yellow LED indicating short circuit detection on one of the signals LT-6041 Rev 3...
  • Page 6 In that kind of system, supervision is not used for the signal lines: The 70V line is supervised by the existing panel and the background music is not an alarm feature. The jumpers will be set as follow on the QIF-2011: Remove Z1,Z2,Z3,Z4 jumper pairs...
  • Page 7: Material Required

    Material required: In addition to the basic material required for QX-5000 operation, a QIF-2000 must be used to provide zone selection specific to either external paging or background music. A 3.9K End of line resistor must be installed at the fire alarm panel to provide supervision for the command line for the external emergency paging signal.
  • Page 8 WIRING: The following diagrams provide wiring information for the QIF-2011 for the typical configuration described above. Figure 3: QIF-2011 connection on signal side for the typical system described. Please see text for other possibilities. LT-6041 Rev 3...
  • Page 9 Figure 4: QIF-2011 to QIF-2000, QIF-5000 and Fire-Alarm panel connections for typical system described above. See text and figure 7 for other configurations. Note: Only connections used for the QIF-2011 are shown. For other connections on the QIF-5000B J3 to J5 terminal blocks please consult QX-5000 manual (Mircom document number LT-616).
  • Page 10 Figure 5: QIF-2011 to QIF-5000B wiring for signal lines for any signal configurations. Note: only connections used for the QIF-2011 are shown. For other connections on the QIF-5000B J1 and J2 terminal blocks please consult QX-5000 manual (Mircom document number LT-616).
  • Page 11 Figure 6: QIF-2011 to QMP-510X connections for any signal configuration. Note: only connections used for the QIF-2011 are shown. For other connections on the QMP-510x terminal blocks and connectors please consult QX-5000 manual (Mircom document number LT-616). LT-6041 Rev 3...
  • Page 12 If only all-call is required for all external signals, connection to a QIF-2000 is not necessary and the QIF-2011 can be connected to opto-input #3 or 4 on the QIF-5000B if those are free. The configuration would be modified as follow:...
  • Page 13 ANC-5000 must be done as per figure 8. Priority jumpers must be removed and jumper JW27 on the QIF-2011 must be set as shown. Also, jumpers JW7 and JW8 must be installed on the ANC-5000. The basic scheme shown is suitable for all call operation of the FleXNet.
  • Page 14: Electrical Characteristics

    Figure 8: QIF-2011 to ANC-5000 connections Electrical characteristics ITEM VALUE Current consumption 40mA @24VDC Signal inputs normal voltage (Rx to Hx) 2.2V +- 10% Control input normal voltage (Cx to Mx) 2.2V +- 10% Signal inputs open circuit detection voltage (Rx to Hx) 4.1V +- 10%...
  • Page 15: Revision History

    Maximum voltage at high voltage signal inputs 2 and 4 100VRMS Revision History Nov 20, 2010: Original June 22, 2011: Revised for rev2 boards spinout and renaming to QIF-2011 July 17, 2012: Added section on ANC-5000 connection. LT-6041 Rev 3...