ABB Relion 615 Series Protocol Manual page 29

Dnp3 communication
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

1MRS756709 D
Parameter
Values (Range)
UR mode
UR retries
UR TO
UR offline interval
UR Class 1 Min events
UR Class 1 TO
UR Class 2 Min events
UR Class 2 TO
UR Class 3 Min events
UR Class 3 TO
Legacy master UR
Legacy master SBO
Default Var Obj 01
Default Var Obj 02
Default Var Obj 30
Default Var Obj 32
615 series
Communication Protocol Manual
Unit
1=Disable
2=Enable
0...65535
0...65535
ms
0...65535
min
0...999
0...65535
ms
0...999
0...65535
ms
0...999
0...65535
ms
1=Disable
2=Enable
1=Disable
2=Enable
1...2
1...2
1...4
1...4
Step
Default
1=Disable
1
3
1
5000
1
15
1
2
1
50
1
2
1
50
1
2
1
50
1=Disable
1=Disable
1
1
1
2
1
2
1
4
Section 4
DNP3 parameters
Description
Unsolicited responses mode
Unsolicited retries before switching to
UR offline mode
Unsolicited response timeout
Unsolicited offline interval
Min number of class 1 events to
generate UR
Max holding time for class 1 events to
generate UR
Min number of class 2 events to
generate UR
Max holding time for class 2 events to
generate UR
Min number of class 3 events to
generate UR
Max holding time for class 3 events to
generate UR
Legacy DNP master unsolicited mode
support. When enabled relay does not
send initial unsolicited message.
Legacy DNP Master SBO sequence
number relax enable
1=BI; 2=BI with status.
1=BI event; 2=BI event with time.
1=32 bit AI; 2=16 bit AI; 3=32 bit AI
without flag; 4=16 bit AI without flag.
1=32 bit AI event; 2=16 bit AI event;
3=32 bit AI event with time; 4=16 bit AI
event with time.
23

Advertisement

Table of Contents
loading

Table of Contents