6.4 Parameter menu
Parameter
Parameter
no.
name
P.26
INP1
P.27
INP2
P.28
INP3
P.29
INP4
P.30
AL I1
P.31
AL I2
P.32
AL I3
P.33
AL I4
P.34
do I1
P.35
do I2
P.36
do I3
P.37
do I4
P.38
bUSNr
6.4.2

Setting parameters

Introduction
All parameters can be set in the parameter menu.
Procedure
The procedure for setting a parameter is as follows:
1. Press the <PAR> key for 5 seconds.
6-8
Adjustment/display range
OFF
24v
¬24V
0-20
4-20
20-0
20-4
noPA
As P.26
As P.26
As P.26
-5.0% to 105.0%
-5.0% to 105.0%
-5.0% to 105.0%
-5.0% to 105.0%
oFF, do1, do2, do3, do4, do5,
do6, ¬do1, ¬do2, ¬do3, ¬d04,
¬do5, ¬do6
As P.34
As P.34
As P.34
0 to 126
"MEnu" and "PARAM" are shown in the middle section of the digital display. "MEnu"
flashes. After these 5 seconds, the appearance of the digital display is as shown below.
Factory
Comment
setting
Function of universal input 1:
oFF
No function
24 V-Digital signal >7 V -> High
¬24 V-Digital signal <4,5 V -> High
Analog signal 0 to 20 mA->0 to 100%
Analog signal 4 to 20 mA->0 to 100%
Analog signal 20 to 0 mA->0 to 100%
Analog signal 20 to 4 mA->0 to 100%
Parameter block
Function of universal input 2
Function of universal input 3
Function of universal input 4
105.0%
Universal input 1 alarm
(analog current function only)
105.0%
Universal input 2 alarm
(analog current function only)
105.0%
Universal input 3 alarm
(analog current function only)
105.0%
Universal input 4 alarm
(analog current function only)
oFF
Status signal assignment
Universal input 1
oFF
Status signal assignment
Universal input 2
oFF
Status signal assignment
Universal input 3
oFF
Status signal assignment
Universal input 4
126
PROFIBUS address
SITRANS DA400 with protection against explosion
Operating Instructions, 02/2006, A5E00684661-01