Installing Sto - Danfoss VLT FC Series Operating Manual

Safe torque off
Hide thumbs Also See for VLT FC Series:
Table of Contents

Advertisement

Safe Torque Off
Operating Guide

3.2 Installing STO

For motor connection, AC mains connection, and control wiring, follow the instructions for safe installation in the Operating Guide
of the drive. See
2.5 Safety Precautions
112, see
3.3 Installation in Combination with VLT® PTC Thermistor Card MCB
Procedure
1.
Remove the yellow jumper wire between control terminals 37 and 12 or 13.
Cutting or breaking the yellow jumper is not sufficient to avoid short-circuiting, see jumper in
Illustration 1: Jumper between Terminals 12/13 (24 V) and 37 (all Drives Except FCD 302)
Illustration 2: Jumper between Terminals 13 (24 V) and 37 (FCD 302)
2.
For example, connect an external safety monitoring relay via an NO safety function to terminal 37 (STO) and either terminal
12 or 13 (24 V DC).