Briggs & Stratton Fortress 10kW Installation And Operation Manua page 37

10kw single phase air-cooled standby generator system
Hide thumbs Also See for Fortress 10kW:
Table of Contents

Advertisement

Available languages

Available languages

Standard Operation:
Wireless Monitor Status LED's
• The wireless monitor receives data from the
generator every 10 minutes and displays the
generator status through 3 LED's.
• Pressing the SYSTEM UPDATE button will provide
current generator status by flashing the status
LED's. When pressed, all 3 LEDs will flash until the
generator status is received.
Monitor/Generator
NOTICE Generator control panel must be in AUTO mode
or no communication with monitor will occur.
Status Codes
• In order to conserve power and to extend battery
life, the LED's are not lit continuously; instead they
are briefly flashed as indicated below.
NOTICE During the weekly exercise cycle, the generator
will run for 20 minutes, but it will not supply power to the
home. During the exercise cycle, the monitor will continue
blinking the GENERATOR READY green LED.
• GENERATOR READY - When active, the green LED
COLOR / ICON
will flash once every 7 seconds. The green LED
green
indicates that the generator is in AUTO mode and
that it is ready to run in the event of a loss of utility
green
power.
• GENERATOR POWER - When active, the green
red
LED will flash every 7 seconds. The green LED
indicates that the generator is supplying power.
BUTTON
• SERVICE NEEDED - When active, the red LED will
flash in a sequence that corresponds to the service
Generator Status
code. For example, when Low Frequency scrolls
across the control board, the red LED will flash 5
The wireless monitor receives data from the generator
times with a 3 second pause between series of
every 10 minutes and displays the generator status
blinks until it is reset or the condition is corrected.
through 3 status icons
Contact the nearest authorized service dealer if the
Pressing the SYSTEM UPDATE button will provide
problem can not be fixed.
current Generator Status by flashing the status icons.
When pressed, all 3 icons will flash until the generator
status is received.
NOTICE Service conditions will only be displayed on the
basic monitor when the control board is placed in AUTO
mode.
GENERATOR READY - When active, the shield
icon will flash green once every 7 seconds. The
green shield icon indicates that the generator is
in AUTO mode and that it is ready to run in the
Installation Inspection
event of a loss of utility power.
GENERATOR POWER - When active, the power
Before placing the generator system into service, inspect
icon will flash green every 7 seconds. The green
the entire installation carefully, utilizing the Installation
power icon indicates that the generator is
Checklist that comes separately inside the literature pack
supplying power.
that is included this manual.
SERVICE NEEDED - When the wrench icon
This completes the installation and start-up instructions.
flashes red, refer to the service codes on the
The operator's manual provides full details on Operation,
back of the monitor or to the troubleshooting
Maintenance and Troubleshooting for this generator
guide in the generator manual. Call the nearest
system.
authorized service dealer if problem cannot be
fixed.
GENERATOR READY
GENERATOR POWER
SERVICE NEEDED
SYSTEM UPDATE
Other:
LED Lighting Codes
No status LEDs illuminated - Generator in OFF
mode or check and replace batteries.
Wireless communication lost issues can typically be
resolved by moving the wireless monitor closer,
within the home, to the standby generator. See
Optional Router Accessory Kit
Batteries Inserted - the shield LED will light for 5
seconds.
• Linking Error or Not Linked - Each icon will light
then turn off in one direction, then the other direction
Linking Error or Not Linked - Each LED will light then
until a successful link is completed.
turn off in one direction, then the other direction
until a successful link is completed.
• During the weekly exercise cycle, the generator
will run for 20 minutes, but it will not supply power to
During the weekly exercise cycle, the generator
the home. During the exercise cycle, the monitor will
will run for 20 minutes, but it will not supply power to
continue blinking the green shield icon.
the home. During the exercise cycle, the monitor
will continue blinking the green shield LED.
Service Code Descriptions - name and number of
flashes are listed on the back side of the wireless
Service Code Descriptions - name and number of
monitor.
flashes are listed on the back side of the wireless
monitor.
XXXXX
XXXXX
None of the service needed codes are cleared at
None of the service needed codes are cleared at the
the wireless monitor. All alerts must be cleared at
wireless monitor. All alerts must be cleared at the
the generator control panel.
generator control panel.
Optional Router Accessory Kit
The monitor has a line of sight range of up to 200 feet,
but this distance will decrease if the signal has to pass
through walls or other objects.
If upon installation and setup of the wireless monitor
system communication is not reliable, Optional Router
Accessory Kit may be needed. See Authorized Dealer
for more information.
The router is a small extender that can be used to
expand the range of a generator wireless network so
XXXXX
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents