1MRS756785 A
Section 3
3.1
REM630
Application Manual
REM630 variants

Presentation of preconfigurations

The 630 series IEDs are offered with optional factory-made application
preconfigurations. The preconfigurations contribute to faster commissioning and
less engineering of the IED. The preconfigurations include default functionality
typically needed for a specific application. Each preconfiguration is adaptable
using the Protection and Control IED Manager PCM600. By adapting the
preconfiguration the IED can be configured to suit the particular application.
The adaptation of the preconfiguration may include adding or removing of
protection, control and other functions according to the specific application,
changing of the default parameter settings, configuration of the default alarms and
event recorder settings including the texts shown in the HMI, configuration of the
LEDs and function buttons, and adaptation of the default single-line diagram.
In addition, the adaptation of the preconfiguration always includes communication
engineering to configure the communication according to the functionality of the
IED. The communication engineering is done using the communication
configuration function of PCM600.
If none of the offered preconfigurations fulfill the needs of the intended area of
application the 630 series IEDs can also be ordered without any preconfiguration.
This option enables full flexibility to configure the IED from the ground up.
The functional diagrams describe the IED's functionality from the protection,
measuring, condition monitoring, disturbance recording, control and interlocking
perspective. Diagrams show the default functionality with simple symbol logics
forming principle diagrams. The external connections to primary devices are also
shown, stating the default connections to measuring transformers. The positive
measuring direction of directional protection functions is towards the motor feeder.
The functional diagrams are divided into sections which each constitute one
functional entity. The external connections are also divided into sections. Only the
relevant connections for a particular functional entity are presented in each section.
Protection function blocks are part of the functional diagram. They are identified
based on their IEC 61850 name but the IEC based symbol and the ANSI function
number are also included. Some function blocks, such as PHHPTOC, are used
several times in the configuration. To separate the blocks from each other, the IEC
61850 name, IEC symbol and ANSI function number are appended with a running
number, that is an instance number, from one onwards.
Section 3
REM630 variants
21