Binary Recording And Led Configuration - ABB Relion 630 Series Applications Manual

Motor protection and control
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 3
REM630 variants
3.2.9
40

Binary recording and LED configuration

All of the start and operate outputs from the respective protection functions,
various alarms from supervision functions, and important signals from control and
protective functions are connected to a binary recorder. In case of a fault, the
binary recorder is triggered which in turn will record all the signals connected to
the recorder.
Table 11:
Signals connected tot the binary recorder
Channel ID
Description
Channel 1
Start of overcurrent low stage
Channel 2
Operate of overcurrent low stage
Channel 3
Start of instantaneous overcurrent stage
Channel 4
Operate of instantaneous overcurrent stage
Channel 5
Start of negative-sequence overcurrent stage 1
Channel 6
Operate of negative-sequence overcurrent stage 1
Channel 7
Start of negative-sequence overcurrent stage 2
Channel 8
Operate of negative-sequence overcurrent stage 2
Channel 9
Thermal overload prior alarm
Channel 10
Operate thermal overload
Channel 11
Start of low stage earth-fault protection
Channel 12
Operate of low stage earth-fault protection
Channel 13
Start of high stage earth-fault protection
Channel 14
Operate of high stage earth- fault protection operate
Channel 15
Operate of phase reversal protection
Channel 16
Operate of loss of load protection
Channel 17
Start of positive-sequence overvoltage protection
Channel 18
Operate of positive-sequence overvoltage protection
Channel 19
Start of positive-sequence under voltage protection
Channel 20
Operate of positive-sequence under voltage protection
Channel 21
Start of negative-sequence over voltage protection
Channel 22
Operate of negative-sequence over voltage protection
Channel 23
Operate of motor jam protection
Channel 24
Operate signal for stalling protection
Channel 25
Operate signal for thermal stress (IIT)
Channel 26
Restart inhibit for motor
Channel 27
Emergency start of motor activated
Channel 28
Motor restart inhibit due to negative-sequence overcurrent protection stage 1
Channel 29
Motor restart inhibit due to negative-sequence overcurrent protection stage 2
Channel 30
Motor restart inhibit due to thermal overload
Channel 31
Circuit breaker closed
Channel 32
Circuit breaker is open
Table continues on next page
1MRS756785 A
REM630
Application Manual