ABB Relion 630 Series Applications Manual page 45

Motor protection and control
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

1MRS756785 A
REM630
Application Manual
All analog input channels are connected to the analog disturbance recorder. When
any of these analog values violate the upper or lower threshold limits, the recorder
unit is triggered which in turn will record all the signals connected to the recorder.
Table 10:
Signals connected to the analog recorder
Channel ID
Description
Channel 1
Phase A current
Channel 2
Phase B current
Channel 3
Phase C current
Channel 4
Neutral current
Channel 5
Phase A voltage
Channel 6
Phase B voltage
Channel 7
Phase C voltage
Channel 8
Neutral voltage
Data connected to analog channels contain 20 samples per cycle.
GUID-0702CD3B-BCC8-47AC-8610-983D014FBFE0 V1 EN
Figure 15:
Measurement and analog recording functions
Section 3
REM630 variants