Technical Data; Device Data; Maximum Ratings Of Outputs - Igema DLT2 Installation And Operating Instructions Manual

Continuous water level transmitter
Table of Contents

Advertisement

7.

Technical Data

7.1 Device data

Manufacture in accordance with: EU-Directive 2014/68/EU
applied standards:
Other Technical Regulations:
Supply voltage:
Power consumption:
Data exchange:
Electrical connection:
Protection class:
Device fuse:
Allowable ambient temperature: 0°C bis 55°C
Supply voltage probe:
Self-test
Service life probe:
The total length of lead:

7.2 Maximum ratings of outputs

Power interface
(not galv. insulated)
Limit and Failure
relay
18
EN 13445-1, EN 61326-1, EN 61010-1
EN 12952-11, EN 12953- 9
Water level 100 - dated February 2010
230V AC (-15% +10%), 50/60Hz
3VA
digital measurement value output
12-pole Screw terminal strip
IP40 in accordance with DIN EN 60529
(protection class IP54 is to be ensured in the boiler area)
63 mA/T
short-circuit-proof, 24V / 2W
alle 3sec
The service life of the probe depends on the operating
conditions and state of the boiler water.
max. 250m
Output current
Load
Switching voltage
(max.)
Switching current
(max.)
4 mA .. 20 mA
max. 500 Ω
250 VAC
4 A ohmic
inductive / higher loads: use contactor
24 VDC
4 A