6.6 Programming of the overfill protection (DLT3)
The overfill level cannot be below the level of the return value!
The return value cannot be above the overfill level!
Caution
Activate the programming menu by pressing „OK". Switch to main menu
„▼"
or
and press button
as per chap. 6.4.
Switch to menu item "Activation Overfill protection" (2.6.) via the buttons
„OK".
„0 0 0."
Change the value
Choose menu item "Overfill limit level (%) / LIMIT" (2.8.) via the buttons
„OK".
Display: → 0X.XX (The grey area is the viewable area of the display / X means a value of
0-9)
„▲"
The buttons
(value of return level) or
for the LIMIT. After pressing
Enter the desired LIMIT value e.g.
„OK".
Choose menu item „return level (%)" (2.7.) via the buttons
Display: → 0X.XX (The grey area is the viewable area of the display / X means a value of
0-9)
„▲"
The buttons
(0%) or
the return level. After pressing
Enter the desired return level e.g.
„OK".
The return level is the value at which the DLT3 return to normal operation
and thus the output relay returns into the normal operation mode (relay
contacts 3 and 5 closed).
Caution
„OK"
2 times. You have reached menu item 2.1.. Enter password (123)
„0 0 1."
to
(buttons
„▼"
„OK"
the display is
„075"
for 75% and press „OK". You reach the last digit via
„▼"
(value of overfill limit) are a quick way to set the starting point for
„OK"
the display is
„070"
for 70% and press „OK". You reach the last digit via
„▲"
or „▼") and press „OK".
(100%) are a quick way to set the starting point
0XX.X
.
„▲"
„▼"
or
0XX.X
.
„▲"
2.
via the buttons
„▲"
„▼"
or
and press
„▲"
„▼"
or
and press
and press „OK".
17