5.3.3 Cable evaluator - probe

For the cable, a 4-core, twisted, shielded cable (4 x 0.5mm2 or 4 x 0.75mm2) must be used.
The side for connection to the evaluator must be assembled with end sleeves and the side for
connection to the probe with a socket (GDME 3011 4-pole).
The shield is to be fitted over a large area in the distribution cabinet on the earthing point.
Connection layout:
Evaluator
9
10
11
12
The total length of the lead must be a maximum of 250m.
When installing care must be taken that, depending on the cable used, the
UV protection is ensured on the installation side if necessary.
The cable must not come into contact with heat-conducting parts.
Caution

5.3.4 Connecting the probe

The probe is equipped with a plug connector (GSP 4-pole). It is connected to the evaluator via
the cable.
5.3.5 Power interface 4 mA .. 20 mA
For the 4 mA .. 20 mA power interface a shielded data line (e.g. LIYCY 0.5mm2) is to be
used.
The load may be max. 500Ω.
14
Socket
+24V
3
GND
CANH
1
CANL
2
1
CANH
2
CANL
3
+24V
GND
GDME 3011 4-polig