Installation; Electrical Connection - Igema DLT2 Installation And Operating Instructions Manual

Continuous water level transmitter
Table of Contents

Advertisement

5.2 Installation

Ensure protection class in accordance with current regulations
Danger
- With quick fastening with spring catch for standard DIN EN 50022 35 mm carrier rail
Fix device on standard carrier rail by means of the quick fastening with spring catch (4).
Release fixing screws (3) and pull hood (7) from base (5).
- Without quick fastening with spring catch
Release fixing screws (3) and pull hood (7) from base (5).
Release screws (1) and remove snap fastening (4). Drill through the marked point (2) in
the base (5) with ø 4.3 mm drill bit.
Fit holder (5) on base plate with two M4 screws.

5.3 Electrical connection

The terminal strip of the device is live during operation!!
Before working on the device, disconnect it from the power supply!!
Danger
The device must be protected mains-side by the operator with a max. T M
2A fuse!
If inductive consumers are connected, voltage peaks occur when
switching off. For this reason, connected inductive consumers (e.g.
Danger
contactor) must be provided additionally with an RC circuit: e.g. 0.1µF /
100Ω.
12