ALARM  2  DISPLAY  COLOR  SUBMENU:
Press     d  
Press     b    
Press     d  
 
IN  ORDER  TO  DISPLAY  ONE  COLOR,  SET  THE  SAME  DISPLAY  
COLOR  ON  ALL  THREE  SUBMENUS  ABOVE.
 
 
If  user  wants  the  display  to  change  color  every  time  that  both  Alarm  
1  and    Alarm  2  are  triggered,  the  Alarm  values  should  be  set  in  such  
a  way  that  Alarm  1  value  is  always  on  the  top  of  Alarm  2  value,  
otherwise  value  of  Alarm  1  will  overwrite  value  of  Alarm  2  and  
Display  Color  would  not  change  when  Alarm  2  is  triggered.
Example  1:  
Alarm  Setup:  Absolute,  Above,  Alarm  2  HI  Value  "ALR.H"  =  212,  
Alarm  1  Below,  LO  Value  "ALR.L"  =  32
"Color  Display"  Setup:  Normal  Color  "N.CLR"  =  Green,  Alarm  1  Color    
"1.CLR"  =  Amber,  Alarm  2  Color  "2.CLR"  =  Red
Display  Colors  change  sequences:
                                 AMBER                          |                        GREEN                    |                                RED
• -­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­ • -­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­ • -­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­
0                                                                  AL1.L  =  32                                AL2.H  =  212                                                  
                                 AMBER                          |                        GREEN                    |                                RED
• -­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­ • -­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­ • -­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­
0                                                                  AL1.L  =  32                                AL2.H  =  212                                                  300      
 
Example  2:
Alarm  Setup:  Absolute,  Below,  Alarm  2  Low  Value  "ALR.L"  =  300,    
Alarm  1  Low  Value    "ALR.L"  =  100
Color  Display  Setup:  "N.CLR"  =  Green,  "1.CLR"  =  Amber,  "2.CLR"  =  
Red
Display  Colors  change  sequences:
         AMBER      |                                  RED                                  |                                              GREEN  
• -­-­-­-­-­-­-­-­-­-­-­-­-­-­ • -­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­ • -­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­-­ -­-­ •
0                          AL1.L  =  100                                            AL2.L  =  300  
11)  Display  flashes  previous  selection  for  "Alarm  2  Color  Display".
12)  Scroll  through  the  available  selections:   GRN ,   RED  or   AMBR .
13)  Display  shows   STRD  stored  message  momentarily  and  
then  momentarily  shows  the  software  version  number,  followed  
by   RST  Reset,  and  then  proceeds  to  the  Run  Mode.
34