Introduction & basic installation

Advertisement

Basic System Commissioning
On/Off operation input
Module Controller / DMS or External contact
Water temperature setting input
Module Controller / DMS or External contact
Operation mode (Cool/Heat, Normal/Hot water) input
Module Controller / DMS or External contact
Demand control input
Module Controller / DMS or External contact
Power Demand Level – Default 100%
Selectable from 50% to 95%
Quiet function input
Module Controller / DMS or External contact
Quiet function level
100% Default
Level 1 – Level 2 – Level 3
Forced fan function input
Module Controller / DMS or External contact
"Water Law" input
Module Controller / DMS or External contact
"Water Law" control standard
Outdoor ambient/Room temperature
Setting Hydro Unit Options
"Water Law" Air Cool 1 – Air Cool 2
"Water Law" Room Cool 1 – Room Cool 2
"Water Law" set temp Tcool 1- Tcool 2
"Water Law" OD temp for Heat AirHeat1 – AirHeat2
"Water Law" Room Heat1 – Room Heat2
"Water Law" set temp Theat1 – Theat2
Remote error reset input
Enable/Disable
Setting unit address – 0 to 15 each unit
Confirm delay for unsecured water flow rate
10 to 240 sec. (factory default 30 sec.)
External water outlet temperature sensor
Enable/Disable (Default)
Operation On/Off by external contact
Low water temperature function (requires antifreeze)
Disable(Default)/Enable