Basic System Commissioning
▪
On/Off operation input
▪
Module Controller / DMS or External contact
▪
Water temperature setting input
▪
Module Controller / DMS or External contact
▪
Operation mode (Cool/Heat, Normal/Hot water) input
▪
Module Controller / DMS or External contact
▪
Demand control input
▪
Module Controller / DMS or External contact
▪
Power Demand Level – Default 100%
▪
Selectable from 50% to 95%
▪
Quiet function input
▪
Module Controller / DMS or External contact
▪
Quiet function level
▪
100% Default
▪
Level 1 – Level 2 – Level 3
▪
Forced fan function input
▪
Module Controller / DMS or External contact
▪
"Water Law" input
▪
Module Controller / DMS or External contact
▪
"Water Law" control standard
▪
Outdoor ambient/Room temperature
Setting Hydro Unit Options
"Water Law" Air Cool 1 – Air Cool 2
▪
"Water Law" Room Cool 1 – Room Cool 2
▪
"Water Law" set temp Tcool 1- Tcool 2
▪
"Water Law" OD temp for Heat AirHeat1 – AirHeat2
▪
"Water Law" Room Heat1 – Room Heat2
▪
"Water Law" set temp Theat1 – Theat2
▪
▪
Remote error reset input
▪
Enable/Disable
▪
Setting unit address – 0 to 15 each unit
▪
Confirm delay for unsecured water flow rate
▪
10 to 240 sec. (factory default 30 sec.)
▪
External water outlet temperature sensor
▪
Enable/Disable (Default)
▪
Operation On/Off by external contact
▪
Low water temperature function (requires antifreeze)
▪
Disable(Default)/Enable
47