Samsung DVM Chiller Training page 37

Introduction & basic installation

Advertisement

Chiller Basic Installation
Basic Installation Clearances
The minimum unit clearances are based on maximum outdoor ambient temperature of 95°F
Above 95°F the clearances should be increased
Single or multiple units with no wall enclosure should have ≥4 inch clearance on sides and rear
Single unit within a wall enclosure should have ≥12 inch clearance on the rear and ≥4 inches each side
Multiple units within a wall enclosure should have ≥12 inches on rear - ≥ 16 inches between units - ≥4 inches
on the side next to the wall
≥ 4 inches
Front
≥ 20 inches
≥ 4 inches
≥ 4 inches
Outdoor Unit Placement
≥ 12 inches
Front
≥ 20 inches
≥ 4 inches
NOTE: Refer to the installation manual for all unit placement requirements
≥ 12 inches
≥ 4 inches
≥ 16 inches
≥ 16 inches