Chiller System Components
Closed loop expansion tank
▪
Expansion tank must be installed on the inlet side of the circulating
water pump above the highest point in the system
▪
Expansion tank sizing: 5% of the total amount of circulating water
in the system
1
Water Side System Components – Field Supplied
Expansion tank example only