Samsung DVM Chiller Training page 13

Introduction & basic installation

Advertisement

DVM Chiller Introduction
Water Law Control – Applications where efficiency is increased by resetting the leaving water
temperature based on outside ambient temperature or room temperature
When chiller is configured for standard water temperature range (default) the operating water
temperature range in cooling will not drop below 41°F
When chiller leaving water temperature is controlled by room temperature, a field supplied TP100
external sensor must be used or a signal from a BMS control
By Outside Temperature
TCool1
TCool2
AirCool1
AirCool2
Ambient Temp.
[Cooling Mode]
DVM Chiller Operation Control Patterns
THeat1
THeat2
AirHeat1
AirHeat2
Ambient Temp.
[Heating Mode]
By Room Temperature
TCool1
TCool2
RoomCool1
RoomCool2
Room Temp.
[Cooling Mode]
THeat1
THeat2
RoomHeat1
RoomHeat2
Room Temp.
[Heating Mode]
13