Basic System Commissioning
Trial Operation
▪
With system off including pump, perform water pressure sensor calibration
procedure
▪
Press & hold K4 and K6 for 3 seconds to start calibration
▪
Calibration will finish automatically within 30 seconds
▪
Verify water circulation and air purged
▪
Verify water flow rate
▪
Mode of operation function
▪
Complete all required Hydro Controller settings
▪
DIP Switch #1 is ON
▪
DIP Switch #2 ON – Cool
▪
Operation control
▪
Press K1 for ON then press K2 for off
▪
Set DIP Switches #1&2 to OFF
▪
Press & hold K5 and K6 for 3 seconds to reset hydro controller
Mandatory Operation Settings
OFF-Heat
K1 K2 K3 K4 K5 K6
48