Download Print this page

olympia electronics GRL-29 WP Manual page 4

Waterproof addressable self-testing non-maintained emergency luminaire

Advertisement

INSTALLATION PROCEDURE (wall installation only)
Mounting holes
Cover
retaining
screws
LAMP FAULT
BATT. FAULT
indicator
TEST
button
1. Use the supplied mounting accessories to mount the device.
2. Remove the four cover retaining screws.
3. Always use in any case round mains cable, with external diameter of 6-9mm (H05RN-F type
2x1mm² or any other type, at least equal to it's mechanical and electrical properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is important to
ensure the tightness isolation IP65). Install the cable gland, pass the round cable through and
tighten it all the way.
4. Connect the cables to the respective positions in the terminal block L for phase and N for neutral.
5. Drill a hole with a diameter of 17mm from the other side of the luminaire. Install the cable grommet
and pass the 2 signal cables.
6. Connect the address cables, in the terminal block with the indicating polarity.
7. Set the luminaire's address through the DIP switch. See table at pages 5 to 7.
8. Install the battery cable connectors to the batteries taking care of the polarity, black cable (-) and red
cable (+).
9. Reinstall the front cover and fasten the retaining screws. (Tightening torque 1Nm).
Pay attention to the 4 sealing o-rings.
WARNING!!
After the installation has finished, charge the batteries for at least 24 hours so as to obtain the
rated autonomous duration.
Page 4 from 7
POWER
CHARGE
indicator
5
4
8
L
L
L
6
L
N
GR-6500 Loop
L
7
ON
1
2 3 4 5 6 7 8
Dipswitch
Position
923029012_09_001

Advertisement

loading

This manual is also suitable for:

Grl-29 adr