Troubleshooting - Carrier 40MAHB Series Installation Instructions Manual

Hide thumbs Also See for 40MAHB Series:
Table of Contents

Advertisement

TROUBLESHOOTING

For ease of service, the systems are equipped with diagnostic code display LEDs on both the indoor and outdoor units. The indoor
diagnostic display is a combination of flashing LEDs on the display panel or the front of the unit.
Some indoor units display error codes specifying failure modes in the outdoor units. If possible, always check the diagnostic codes displayed on
the indoor unit first.
The diagnostic codes displayed in the indoor and outdoor units are listed in Table 9.
INDOOR UNIT DIAGNOSTIC GUIDES
OPERATION LAMP (TIMES)
1
2
3
4
5
5
5
5
5
6
6
12
9
8
7
2
3
5
1
6
7
1
9
11
For additional diagnostic information, refer to the service manual.
40MAHB-01SI
Table 9 —
Indoor Unit Diagnostic Codes
TIMER LAMP
DISPLAY
OFF
EH 00/EH 0A
OFF
EL 01
OFF
EH 02
OFF
EH 03
OFF
EC 51
OFF
EC 52
OFF
EC 53
OFF
EC 54
OFF
EC 56
OFF
EH 60
OFF
EH 61
OFF
EC 07
OFF
EH 0b
OFF
EL 0C
FLASH
PC 00
FLASH
PC 01
FLASH
PC 02
FLASH
PC 04
FLASH
PC 08
FLASH
PC 40
FLASH
PC 03
ON
--
OFF
EH b1
OFF
FH 0d
O (on − light) X (off − light) ☆(flash)
Specifications subject to change without notice.
ERROR INFORMATION
Indoor unit EEPROM parameter error
Indoor/outdoor unit communication error
Zero-crossing signal detection error
Indoor fan operating outside of the normal range
Outdoor unit EEPROM parameter error
T3 is in open circuit or has short circuited
T4 is in open circuit or has short circuited
TP is in open circuit or has short circuited
T2B is in open circuit or has short circuited
T1 is in open circuit or has short circuited
T2 is in open circuit or has short circuited
Outdoor fan operating outside of the normal range
Indoor PCB/Display board communication error
Refrigerant leakage detection
IPM malfunction or IGBT OSCP
Over voltage or over low voltage protection
Compressor or IPM high temp/pressure protection
Inverter compressor drive error
Current overload protection
Communication error between outdoor chip and compressor chip
Low pressure protection
Indoor unit mode conflict
Indoor board and Multi-function communication error
Ionizer malfunction