Ductless Start-Up Checklist (CONT)
Piping
Leak Check:
System held 500 psig (max. 550psi) for a minimum of 30 minutes using dry nitrogen. YES:______ NO:______
Evacuation Method:
Was the Triple Evacuation Method used as outlined in the installation manual?
Was the Deep Vacuum Method used as outlined in the installation manual?
Did the System Hold 500 microns for 1 hour?
Does the line set match the diameter of the evaporator connections?
For Conventional Fan Coils, does the line set match the outdoor unit size?
Single Zone Piping:
Has the liquid pipe length been measured and the additional charge calculated? Size:___________ Length:_________ Charge:____________
NOTES:
PORT
LIQUID SIZE
A
Performance Check
For 1:1 Single Zone Systems: Adjust the set-point to create an operational call for the desired testing operation. Allow the system to run for a
minimum of 10 min. and record the following details:
(Operational data recorded on applicable heads with the wireless remote controller's Point Check function)
UNIT
SET-POINT
A
NOTE:
T1 - Ambient Space Temperature Sensor
T2 - IDU Coil Temperature Sensor
T3 - Outdoor Coil Temperature Sensor
T4 - Outdoor Ambient Temperature
Tb - Suction Line Temperature @PMV
Tp - Discharge Temperature Sensor
Th - IPM Board Temperature
LA/Lr - PMV Temperature
Error Codes
Were there any error codes present at start-up?
Indoor Unit Error Code:
Outdoor Unit Error Code:
Wall Controller:
24V Interface:
Comments:
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
Copyright 2020 Carrier Corp D 3300 Riverwood Parkway Atlanta GA, 30339 Edition Date: 12/20
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
SUCTION SIZE
MODE
T1
T2
Notes:
YES:______ NO:______
YES:______ NO:_______
YES:______ NO:_______
YES:______ NO:_______
YES:______ NO:_______
LENGTH
CHARGE
NOTES:____________________________________
___________________________________________
___________________________________________
T3
T4
Tb
YES:______ NO:______
Tp
Th
LA/Lr
Catalog No. 40MAHB-01SI
Replaces: NEW

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents