Step 4 - Prepare Refrigerant Piping - Carrier 40MAHB Series Installation Instructions Manual

Hide thumbs Also See for 40MAHB Series:
Table of Contents

Advertisement

9.1in (230mm)
Left rear wall
hole 2.5in (65mm)
7.3in(185mm)
1.7in(45mm)
31.7in(805mm)
Model B
Fig. 12 — Model B
11.2in(285mm)
Left rear wall
hole 2.5 in (65mm)
1.7in(45mm)
9.5in(240mm)
37.7in(958.3mm)
Fig. 13 — Model C
10.4in(264mm)
1.77in(45mm)
Left rear wall
8.6in(219mm)
hole 2.5in(65mm)
40.85in(1037.6mm)
Fig. 14 — Model D
NOTE: When the gas side connective pipe is 5/8in (16mm
more, the wall hole should be 3.54in (90mm).
DRILL A HOLE IN WALL FOR THE
INTERCONNECTING PIPING, DRAIN AND WIRING
Refrigerant Line Routing
The refrigerant lines may be routed in any of the four directions. For
maximum serviceability, it is recommended to have refrigerant line
flare connections and the drain connections on the outside of the wall
that the fan coil can be mounted on. If piping is going through the
back, determine the pipe hole position using the mounting plate as a
template. Drill pipe hole diameter per values given in figures 11
through 14. The outside pipe hole is 1/2−in. (13 mm) min. lower than
the inside pipe hole, so it slants slightly downward.
10
16.2in(411mm)
9.7in(246mm)
Indoor unit
outline
Right rear wall hole
2.5in(65mm)
5.5in(139mm) 4.2in(107mm)
18in(458mm)
9.57in(243mm)
Indoor unit
outline
Right rear wall hole
3. 9 i n (100mm)
5. 6 in(143mm)
2.5in(65mm)
22in(559mm)
13.5in(344mm)
1.77in(45mm)
Right rear wall hole
11.8in(299mm)
2.5in(65mm)
Φ
) or
Specifications subject to change without notice.

Step 4 - Prepare Refrigerant Piping

The refrigerant piping is inside an insulating sleeve attached to the
back of the unit. The installer must prepare the piping before passing
it through the hole in the wall.
1. Based on the position of the wall hole relative to the mounting
plate, choose the side from which the piping exits the unit.
2. If the wall hole is behind the unit, keep the knock-out panel in
place. If the wall hole is to the side of the indoor unit, remove the
plastic knock-out panel from that side of the unit. This creates a slot
through which your piping can exit the unit. Use needle nose pliers
if the plastic panel is too difficult to remove by hand.
Fig. 15 — Knock-out Panel
3. If the existing connective piping is already embedded in the wall,
proceed directly to "Step 5 - Connect the Drain Hose". If there is no
embedded piping, connect the indoor unit's refrigerant piping to the
connective piping that connects the indoor and outdoor units.
NOTE: Refrigerant piping can exit the indoor unit from four
different angles; left-hand side, right-hand side, left rear, right
rear.
Fig. 16 — Piping Angles
CAUTION
Be extremely careful not to dent or damage the piping while
bending them away from the unit. Any dents in the piping will
affect the unit's performance.
Knock-out Panel
40MAHB-01SI