Schwank UHE Installation & Owner's Manual page 14

High radiant output low intensity tube type infra red heater
Hide thumbs Also See for UHE:
Table of Contents

Advertisement

FIGURE 6 HANGER / REFLECTOR ORIENTATION - HORIZONTAL TO 30
See Elbow Dimensions
~Page 46~
FIGURE 7 HANGER POSITIONING / SPACING (Also see Page 41)
POSITION BURNER END HANGER 6 INCHES (15 CM) FROM TUBE FLANGE
EACH TUBE & REFLECTOR SECTION REQUIRES 2 HANGERS
POSITION INTERMEDIATE HANGERS A MINIMUM OF 2 INCHES (5 CM) TO A MAXIMUM OF
22 INCHES (56 CM) FROM THE EDGE OF ANY TUBE COUPLER
LOCATE VENT END HANGER WITHIN 12 INCHES (30 CM) OF THE END OF THE LAST RE-
FLECTOR
*
ANGLE BURNER SUPPORT CHAIN BACK OVER BURNER TO ALLOW SYSTEM EXPANSION
UHE-F / EIH-F I&O Manual
IM100205
RD: APR 2019
RL: 02C
14