Taking Rain Measurements - Van Walt Rain Gauge Operating Instructions Manual

Table of Contents

Advertisement

VAN WALT
Monitoring your needs
4.2

Taking rain measurements

The datalogger records the number of
contacts made by the rain gauge and
converts those to the amount of rain
in mm. The datalogger has two ways
of processing these contacts. Channel
1 processes the number of contacts,
determines the amount of rain between
two samplings times and stores this value.
Channel 2 is a so-called integrator, that
keeps on recording as the new value,
the new value from channel 1, with the
previous measurement total added to it.
This is called the accumulation of data.
In order to measure the daily amount of rain (the most commonly used procedure) the Sample
speed of the data- logger is set at 24 hours in LDM e+, e-SENSE direct or on the e-SENSE data site. If
a lower Sample speed is selected, a so-called intensity measurement can be taken. Rain intensity
measurements are normally expressed in mm per
hour, and for these the Sample speed needs to be set at 1 hour. An even lower Sample speed
can be selected if the rain intensity needs to be recorded over shorter periods.
e+ Sensors possess an alarm function which activates the alarm status of the sensor when
measurement values exceed a certain pre- determined limit. A device that has been connected
can detect an active alarm status and depending on its function, can respond by performing a
specific task after which it can turn off the alarm status of the datalogger. The alarm function is set
by means of alarm boundaries and hysteresis limits. As soon as the measurement values exceed
one of the alarm boundaries the alarm status is activated.
The alarm status can be reactivated only once the hysteresis limits are reached. The limit values
can be set in LDM e+, but LDM e+ does not support alarm functionality. The relevant settings have
the following meanings:
• AlarmHigh: specifies the high limit that will cause the alarm status to be activated.
• HystHigh: specifies the high limit that will cause the alarm function to be reactivate.
• AlarmLow: specifies the low limit that will cause the alarm status to be activated.
• HystLow: specifies the low limit that will cause the alarm function to be reactivated. (note: the
low limits do not have any practical use when measuring rain)
Van Walt Ltd | Prestwick Lane | Grayswood | Haslemere | Surrey | GU27 2DU | Tel. 01428 661 660 | Fax. 01428 656 808 | www.vanwalt.com
Operating Instructions
Rain Gauge
Alarm High
Hysteresis
High
Alarmstatus
Externe
Heraktlvering
Ultschakeiing
Alarmfunktle
16

Advertisement

Table of Contents
loading

Table of Contents