For the SA fan assembly
[7] Remove the DC motor assembly (SA).
a. Remove the earth lead (green) fixing screw.
(1 screw: PT screw 4x10, indicated by
Tightening torque
: 1.5 ± 0.2 N . m
b. Raise the cord clip fixing the earth lead (green).
c. Remove the earth lead (black) fixing screw.
( 1 screw: PT screw 4x8 (BS) with washer, indicated
by
)
Tightening torque
: 0.96 ± 0.14 N . m
d. Unhook the thermistor (RA) lead from the hooks on
the orifice (indicated by
e. Cut the insulok tie fixing the damper lead and earth
lead (green).
Precaution
Take care not to cut the lead wires.
Assembly precaution
When installing the damper lead and earth lead
(green), be sure to fix them with an insulok tie.
f. Remove the screws.
(4 screws: Spl PPT screw 4x30, indicated by
Tightening torque
: 1.1 ± 0.2 N . m
*There are spacers (4 spacers: 6x15) behind the DC
motor assembly (SA).
g. Remove the DC motor assembly (SA).
Precaution
Be careful not to catch the damper lead and therm-
istor (RA) lead by the notch (indicated by
)
).
)
).
─ 73 ─
Earth lead (green)
Cord clip
DC motor assembly (SA)
Damper lead
Insulok tie
DC motor assembly (SA)
Damper lead
Earth lead (black)
Thermistor (RA) lead
Earth lead (green)
Thermistor (RA) lead