Mitsubishi Electric Lossnay VL-250CZPVU-L-E Handbook page 35

Heat recovery ventilator
Hide thumbs Also See for Lossnay VL-250CZPVU-L-E:
Table of Contents

Advertisement

Error code
LED1
(Controller
(green)
display)
6833
9
Controller com-
blinks
munication error
(hardware error)
6834
9
Controller com-
blinks
munication error
(start bit detec-
tion error)
7113
10
Function setting
blinks
error
Error
Faulty connection of the controller
cable
Faulty connection of the controller
cable
The model selection switch (SW6) is
not set correctly.
Cause
─ 35 ─
Corrective action
Refer to section [2] of "Failure
mode 1".
If the error code does not disap-
pear, investigate noise on the con-
troller cable.
If the problem persists, replace the
control circuit board or controller.
Refer to section [2] of "Failure
mode 1".
If the error code does not disap-
pear, investigate noise on the con-
troller cable.
If the problem persists, replace the
control circuit board or controller.
Check the model selection switch
(SW6).
Refer to (Note 1) in "(3) b. Function
selection switch (page 43)".