Download Print this page
Westinghouse KD Instructions Manual
Westinghouse KD Instructions Manual

Westinghouse KD Instructions Manual

K-dar directional comparison blocking systems

Advertisement

Quick Links

K-DAR DIRECTIONAL COMPARISON
I NT RODU CT ION
This leaflet describes the overall functioning
of K-Dar relays when used in conjunction with a
blocking channel (power line carrier, microwave or
pilot wire).
Detailed description of operation,
as well as setting and maintenance recommendations
for individual relays of the K-Dar directional com­
parison blockiug system are covered in the individual
relay instruction leaflets; the des.eription here is
intemted to supplement these relay instructions.
A PPLIC AT ION
Dir. e ctional comparison blocking is employed to
eliminate delayed clearing of end-zone line faults;
thus, high speed, simultaneous clearing of all line
faults is accomplished.
with current and potential from the protected line
are unable to trip both selectively and at high speed
for line faults near the remote station. By transmitting
a signal from the remote station when the fault is
external to the protected line, the local relays are
blocked
from tripping.
means of intelligence, local relay tripping must be
delayed for internal faults near the remote station,
to insure against undesired tripping when the fault
is on an adjacent circuit near the remote station.
This system can be utilized with minor differ­
ences with either on-off or frequency shift type of
operation over pilot wire tones, microwave or power
line carrier channels .
Blocking of tripping is ef­
fected by either keying on or shifting the transmitter
frequency.
EQUIPMENT
K-Dar is the designation for a group of relays,
which are itemized below:
Directional Fault Detecting Relays
1 -Type KD Directional phase tripping unit,
NEW INFORMATI ON
INSTALLATION
INSTRUCTIONS
BLOCKING SYSTEMS
Protective relays energized
Without
this additional
COMPLEMENT
OPERATION
consisting of:
1 -Phase-to-phase
operates for all three combinations of
phase-to-phase faults anywhere on th e
protected line.
1 - Three-phase unit (ZP-3 ¢).which operates
for 3 phase faults anywhere on the pro­
tected line.
1 -Indicating contactor switch (ICS).
1 -Type KD-1 Directional Phase start unit, con­
sisting of:
1 - Phase-to-phase
reach in the reversed direction to that
of ZP-¢4.
1 - Three phase unit (Zs-3 ¢), set to reach
in the reversed direction to that of ZP-3 ¢.
1 -Indicating contactor switch (ICS).
1 -Type KRD (or KRC, or KRP, or KRQ) Di­
rectional ground tripping unit, consisting of:
1 -Directional unit, current polarized (D 0c )
1 -Directional unit, voltage polarized (D
1 -Instantaneous overcurrent unit ( 1 0 )
1 -Indicating contactor switch (ICS)
&
Auxiliary Relay
Accessories
1 -Type KA Carrier auxiliary relay, consisting
of:
1 -Receiver relay unit (RR). with a holding
coil, RRH, a tripping coil, RRT. and two
contacts, RRG
1 -Phase auxiliary unit (CSP)
1 - Ground auxiliary unit (CS G)
EF F ECT IVE OCTOBER
41-911
I .L.
MAINTENANCE
unit
(ZP-cfxh
which
unit (Z&#).
set
0p )
RRP
&
1959
to

Advertisement

loading
Need help?

Need help?

Do you have a question about the KD and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Westinghouse KD

  • Page 1 1 -Indicating contactor switch (ICS). intemted to supplement these relay instructions. 1 -Type KD-1 Directional Phase start unit, con­ A PPLIC AT ION sisting of: 1 - Phase-to-phase unit (Z&#).
  • Page 2 P R O TECTED L I N E I NTE R N AL FAULT FAULT L�� M A R G I N SET M N )0. 5 NP Fig. Phase Relay SeHings BLOCKING IIII I T OUT OF STEP ALARM UNIT OF KA RELAY (WHEN USED) GROUMO AUXILIARY OF KA RELAY...
  • Page 3 (OS) will be tripped after time delay, T3, if the fault is within the reach of ZP. Backup 2 -KD Phase distance relays (Zones 1 & Ground Fault Tripping Ground directional unit when &...
  • Page 4 In Fig. ZP or contacts close at breaker A whether the fault is internal, or external to the right of breaker B; in either case, CSP or CSG is energized and RRT, in turn, is energized. For the SEC. external fault only, the transmitter at B sends a MIN.
  • Page 5 Table Summarv of OPeration. 'MTR, START CSG COI L S x'MTR, STOP COI L. COIL. TRI P CI R CUIT +� BKR. BKR. + !ZP x ' MTR � _ _2:sG RCVR , & RRG HELD z3 STAYS ENERGIZES BKR. A OPEN BY CLOSES CLOSES...
  • Page 6 unit is energized, and after 4 cycles, an OS c on­ External Ground Fault Operation ¢ tact opens the ZP-3 trip-circuit. All this occurs Refer to Table I. Since the ground overcurrent before the swing reaches point, P, in Fig. 3. �...
  • Page 8 WESTINGHOUSE ELECTRIC CORPORATION NEWARK, N. J. RELAY DEPARTMENT Printed in U. S. A.
  • Page 9: Operation

    1 -Indicating contactor switch (ICS). a signal from the remote station when the fault is external to the protected line, the l�cal relays are 1 -Type KD-1 Directional Phase start unit, con­ blocked from tripping. Without this additional sisting of:...
  • Page 10 TIMER START AUXILIARY UNIT OF TD-2 RELAY DISTANCE UNIT OF KS RELAY ZP-fJ PHASE-TO-PHASE UNIT OF KD RELAY ZP-3f PHASE URI T OF KD RELAY ZS- I f PHASE-TO-PHASE URI T OF KD-1 RELAY zs-3• 3 PHASE UN IT OF Kl)-1 RELAY...
  • Page 11 Backup or external, is not cleared by other means, the breaker will be tripped after time delay, T3, if the fault is 2 -KD Phase distance relays (Zones 1 & within the reach of ZP. 1 -TD-2 Timing relay consisting of:...
  • Page 12 Receiver Relay Comparison Circuits Receiver relay, RR, has an RRH holding coil and an RRT tripping coil as shown in Fig. 2. RRH is energized by the receiver output when a blocking SEC. signal is transmitted; RRT coil is energized when­ M I N.
  • Page 13 K-DAR I.L. 41-911A Table Summarv ol 0Deratlon. START CSP 8 BKR. X'MTR. CSG COILS x'tnR. STOP RRT COIL. RRH COIL. TRIP CI R CUI T +� + :!:zp + !ZP � I o/MTR � _ ,2 SG RCVR, & RRG HELD z3 STAYS BKR.
  • Page 14 ZI·P X· REACTOR SAME NOT USED ZONE. EXCEPT CJc I esc I .:.o. "'"' ZONE '2 z"- 0-0 - S UNIT L----- _J o .. 21·S �§ oo< �� �" �;r � � � � INTERNAL 5CHE'IVIA.TICS DEVICE DWG t.JO. ON O�F iOGoGLE SW.
  • Page 15 C I R C U I T B A. C K· U P BLOCKING IONE 1 � � TRIP PRIMARY RELAYING RELAYING, 0•0•:5 '7NT "i01"Th> 10110) VE'c� '1MT 1(1) Tis) � os os�!f 0· O·S INDICATION POS, 'l.I·P ll>' "'ZP (;�: �.
  • Page 16 Z Load • to the fault of the 1 0s for any fault which will also result in value, represented by the line 0-F in Fig. 3. When 1 0 operation. WESTINGHOUSE ELECTRIC CORPORATION Printed in U. S. A.
  • Page 17 Westinghouse I.L. 41-911C OPERATION MAINTENANCE INSTALL A Tl 0 N • • INSTRUCTIONS K-DAR DIRECTIONAL COMPARISON BLOCKING SYSTEMS IN TRODU CTION the less, the underlying principles described here apply whether or not the back-up protection is inde­ pendent or common with the p rimary protection. Of This leaflet describes the overall functioning course, the relaying complement will vary.
  • Page 18 ZP-3f 3 PHASE UNIT OF K0-4 ZS-ff PHAS E-TO-PHASE UNIT OF K0-41 RELAY ZS-3. 3 PHASE UNIT OF KD-41 RELAY C I RCUIT BREAKER AUXILIARY SWITCH CONTACT- CLOSED WHEN BREAKER IS CLOSED 52TC CIRCUIT BREAKER TI I P COIL SOl'" 78oA7 -43 <00I...
  • Page 19 & Auxiliary Relay Accessories ground faults) permitted to trip. Succeeding paragraphs will explain how this is performed. 1 - Type KA4 Carrier auxiliary relay , cons isting Phase Fault Tripping ¢¢ ¢ & Distance units, ZP (ZP- ZP-3 operate 1 - Receiver relay unit ( RR) , with a holding only when fault power flows into t he prote cted line, coil, RRH, a tripping coil, RRT, and two as s hown in fig.
  • Page 20 Receiver Relay Comparison Circuits Receiver relay, RR, has an RRH holding coil and an RRT tripping coil as shown in Fig. 2. RRH is energized by the receiver output when a blocking signal is transmitted; RRT coil is energized when­ ever the local tripping relay contacts close in an 2 S EC.
  • Page 21 I . L. 41·911C K-DAR Table Summarv of Operation. BI<R. BKR. x 'M TR. CSG COII.S R R H S TART X M T R. S TOP R R T C O I L C O I L T R IP C I RC U I T +�...
  • Page 22 6'."; ' q1:: ::- ���_,�$-,--H-C::J � ,�- 1 ., � __._,---. _. � ---- -- -,_ J J._ I J � SI'/MF .5AME £��-:P7 �1 Z O N E �-R CTOR NOT USED zt:JI3) ZONE Z #, DI.:J,T,IfiVC.f. .J,PDI.!!. 2/-S �...
  • Page 24 so the transmitter s ends a blocking signal. Tripping a swing or o ut-of-step condition occurs t he imped­ does not occur because ZP is open. ance s een by Z & ZP changes gradually , as the voltage decre ases and the current incre as e s .

This manual is also suitable for:

Kd-1KrdKrcKrpKrq