TYPE RC AUTOMATIC RECLOSING RELAY
Before putting relays into service, remove
C A UT I O N
all blocking which may have been inserted for the
purpose of securing the parts during shipment, make
sure that all moving parts operate freely, inspect the
contacts to see that they are clean and close prop
erly, and operate the relay to check the settings and
electrical connections.
APPLICATION
The type RC automatic reclosing relay is used
for automatic reclosure of AC or DC electrically oper
ated circuit breakers after they have been opened by
overcurrent or other protective relay action. The relay
may be adjusted to provide several reclosures at pre
determined time intervals, so that in case the breaker
does not remain closed after the first reclosure addi
tional reclosures will be made.
usually
is an instantaneous reclosure through pre
closed contacts since system operating experience
has shown that the majority of faults are of a tem
porary nature, such as lightning flashovers, and will
not be re-established after interruption of the fault
current.
Consequently,
minimized by the use of an instantaneous reclosure.
However, the first reclosure may be delayed if desired.
In case the circuit breaker does not remain closed
after the first reclosure, the relay will make additional
reclosures at suitably graded intervals. It is common
practice to make two additional reclosures, but the
relay may be adjusted to make any number up to a
total of six reclosures if desired. If the breaker does
not remain closed after the final reclosure, the timing
drum stops in the "Lockout" position, and any further
attempts at reclosure must be made by manual opera
tion of the control switch.
remains closed after any automatic reclosure, or, sub
sequently,
after manual reclosure,
drum will advance to and stop at the "Start" position,
where the relay is in readiness for another cycle of
automatic reclosures following the next tripping of
the breaker.
For any automatic reclosing application, the de
41-661
rating factors for breaker interrupting ability should
SUPERSEDES I. L.
*Denotes change from superseded issue.
I N S T R U C TI O N S
The first reclosure
service interruption can be
However, if the breaker
the relay timing
B
•
Westinghouse
be checked when choosing any particular reclosing
cycle. Also, when using instantaneous first reclosure
it is necessary that the protective relays open their
contacts within
10
cycles or less after the breaker
is tripped in order that the trip circuit will be de
energized before reclosure takes place.
CONSTRUCTION
An additional instantaneous unit,
As shown in figure
latching solenoid unit, Y, a synchronous motor driven
when specified.
T i m i n g U n i t
The timing unit contains a synchronous motor and
gear train mounted behirui the front sub-base.
gear train drives a drum with cams, which actuate
contacts
1 , 2 , 3 , 4
and
1 4 .
latch to reset the Y unit and close the
and # 2 , which operate contacts 1 and
Cams
# 1
respectively, are notched and are not intended to be
#5 consist of screws which can be set at any point on
adjusted
in the field.
springs secured by screws, which can be located at
any point on the periphery of the drum. Cams
the periphery of the drum.
block, located to the rear of the cam
held by a
#5
cam screw.
The gear train reduction ratio is adjustable. The
with an index mark to mesh the proper gears for the
desired drum speed.
A clamping screw is provided at
the edge of this dial.
A push rod is located on the
front of the drum to demesh the drum and permit free
manual drum rotation.
The
dial on the timing drum has
(second intervals with
edges of the
#3, 4
and
spaced white marks corresponding to
tervals with a
60
second drum speed.
EFFECTIVE FEBRUARY 1 959
•
I . L. 41-661C
1 ,
the RC relay consists of a
Z ,
is also provided
The
Cam
5
actuates theY unit
Y13
contact.
Cam
#3
is a series of flat
#4
Cam
#14
is a single micarta
#5
position and
which are lined up
•.
60
divisions
60
second drum speed). The
5
cam slots have
12
equally
5
second in
X.
2
and