Safety Precautions - Bosch Climate 5000 MS 18 Installation Manual

Inverter one-twin/one-three/one-four/one-five split-type air conditioner
Table of Contents

Advertisement

Safety Precautions

2
Safety Precautions
Read Safety Precautions Before Installation
Incorrect installation due to ignoring instructions can cause serious
damage or injury.
The seriousness of potential damage or injuries is classified as either a
WARNING or CAUTION.
WARNING
Failure to observe a warning may result in serious injury. The
appliance must be installed in accordance with national regulations.
CAUTION
Failure to observe a caution may result in injury or equipment
damage.
WARNING
• Carefully read the Safety Precautions before installation.
• In certain functional environments, such as kitchens, server rooms,
etc., the use of specially designed air-conditioning units is highly
recommended.
• Only qualified personnel should install, repair and service this
air conditioning unit.
• Improper installation may result in electrical shock, short circuit,
leaks, fire or other damage to the equipment and personal property.
• Strictly follow the installation instructions given in this manual.
• Improper installation may result in electrical shock, short circuit,
leaks, fire or other damage to the equipment.
• After installation, ensure there are no refrigerant leaks and that the
unit is operating properly. Refrigerant is both toxic and flammable
and poses a serious health and safety risk.
• Do not use means to accelerate the defrosting process or for clean-
ing, other than those recommended by the manufacturer.
WARNING
• The appliance disconnection must be incorporated with an all-pole
disconnection device in the fixed wiring in accordance with the
wiring rules.
• Any person who is involved with working on or breaking into a
refrigerant circuit should hold a current valid certificate from an
industry-accredited assessment authority, which authorises their
competence to handle refrigerants safely in accordance with an
industry-recognised assessment specification.
• Servicing shall only be performed as recommended by the
equipment manufacturer. Maintenance and repair requiring the
assistance of other skilled personnel shall be carried out under
the supervision of the qualified personnel in the use of flammable
refrigerants.
• The appliance shall be stored so as to prevent mechanical damage
from occurring.
• Keep ventilation openings clear of obstruction.
4
NOTE:
The following information is required for units using R32 refrigerant.
• The appliance shall be stored in a room without continuously
operating heat source (for example: open flames, an operating gas
appliance or an operating electric heater).
• Do not pierce or burn the unit.
• Be aware that the refrigerants may not contain an odour.
• Compliance with national gas regulations shall be observed.
• The appliance shall be stored in a well-ventilated area where the
room size corresponds to the room area as specified for operation.
• The appliance shall be installed, operated and stored in a room with
a floor area larger than X m² (see the following form). The appliance
shall not be installed in an unventilated space, if that space is small-
er than X m² (see the following form).
Model (KW)
Amount of
refrigerant to
be charged
(kg)
8.5KW
≤2.048
8.5KW
≤2.048
8.5KW
≤2.048
9KW - 14KW
2.048-3.0
9KW - 14KW
2.048-3.0
9KW - 14KW
2.048-3.0
above 14KW
>3.0
above 14KW
>3.0
above 14KW
>3.0
Table 2.
Note on fluorinated gases
1. This air-conditioning unit contains fluorinated gases. For specific
information on the type of gas and the amount, refer to the relevant
label on the unit itself.
2. Installation, service, maintenance and repair of this unit must be
performed by Qualified Personnel.
3. Product uninstallation and recycling must be performed by Qualified
Personnel.
4. If the system has a leak-detection system installed, it must be
checked for leaks at least every 12 months.
5. When the unit is checked for leaks, proper record-keeping of all
checks is strongly recommended.
Climate 5000 MS – 6720887246 (2018/04)
Maximum
Minimum
installation
room area
height (m)
(m²)
2.2m
4
1.8m
4
0.6m
35
2.2m
4
1.8m
8
0.6m
80
2.2m
5
1.8m
9
0.6m
80