GENERATOR SYSTEM
From page 7-5
Normal
Assemble the all parts to the generator, start
the engine and measure the AC out put
voltage after more 30 minutes.
If the generator does not AC output, replace
the AVR unit and recheck.
7-6
No or low voltage
Disconnect the main winding 4P connector
Normal
Connect a known good 12 v battery to the brush
terminals.
Run the engine at 3,750 min
following voltages at the test points show below.
WINDING
Main winding
Main winding
(signal)
Exciter winding
Replace the rotor and recheck.
From page 7-5
-1
(rpm) and check the
CONNECTOR
TERMINAL No. (COLOR)
2 (Red)
4 (Blue)
3 (Blue)
4 (Brown)
1 (Yellow)
2 (Yellow)
Abnormal
.
VOLTAGE
(Minimum)
94 VAC
8 VAC
40 VAC