netvox R718N3 Series User Manual page 7

Wireless 3-phase current meter
Hide thumbs Also See for R718N3 Series:
Table of Contents

Advertisement

Example of ConfigureCmd
FPort:0x07
Bytes
1
CmdID
CmdID– 1 bytes
DeviceType– 1 byte – Device Type of Device
NetvoxPayLoadData– var bytes (Max=9bytes)
Description
Device
Config
ReportReq
Config
ReportRsp
R718N3
ReadConfig
ReportReq
ReadConfig
ReportRsp
(1) Configure device parameters MinTime = 1min, MaxTime = 1min, CurrentChange = 100mA
Downlink: 014A003C003C0064000000
The device returns:
814A000000000000000000 (Configuration succeeded)
814A010000000000000000 (Configuration failed)
(2) Read device configuration parameters
Downlink: 024A000000000000000000
The device returns:
824A003C003C0064000000 (current device configuration parameters)
1
DeviceType
Device
CmdID
Type
MinTime
0x01
(2bytes Unit:s)
0x81
0x4A
0x02
MinTime
0x82
(2bytes Unit:s)
Var(Fix =9 Bytes)
NetvoxPayLoadData
NetvoxPayLoadData
MaxTime
(2bytes Unit:s)
Status
(0x00_success)
Reserved
(9Bytes,Fixed 0x00)
MaxTime
(2bytes Unit:s)
6
Reserved
CurrentChange
(3Bytes,Fixed
(2byte Unit:1mA)
Reserved
(8Bytes,Fixed 0x00)
Reserved
CurrentChange
(3Bytes,Fixed
(2byte Unit:1mA)
0x00)
0x00)