Function

4.6 Cycle Data View

This function is intended to identify the Cycle data of ODU, which is running on.
The 7 Segment is display 26 different cycle data.
No
1
Current High Pressure
2
Current Low Pressure
3
Inv. Comp.
4
Fan1
5
Fan2
6
Superheating degreee
7
Subcooling degreee
8
ODU temp.
9
Suction temp.
10
Comp. discharge temp.
12
Liquid pipe temp.
14
SC_OUT
15
Hex
18
Inlet pipe average temp. of IDU
19
Main EEV
21
SC EEV
25
IDU running capacity
26
Total number of IDU
Cycle data view function setting method
Service PCB DIP switch on : No.5
Select the mode using
Push the
button
'●'
Select the Function using
Push the
button
'●'
Selec the Option using
Push the
button
'●'
Start the Cycle data view fuction : Display the cycle
data value selected from the Segment.
Title
7-seg
PLS1
PLS3
IDU1
IDU2
Button : "SVC"
' ', ' '
Button : : "Se 8"
' ', ' '
Button : : "op1~op26"
' ', ' '
example
P1
4321 kPa(626.7 psi)
P2
1234 kPa(179 psi)
H1
120 Hz
H3
110 RPM
H4
110 RPM
T1
53
T2
-4.5
T3
10
T4
43.4
T5
150
T7
10
T9
10
T10
10
T13
-10
1950 pls
16 pls
24 KBtu
10 EA
- 32 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Seg_1 Seg_2 Seg_3 Seg_4
4
3
2
1
2
3
1
2
1
1
1
1
5
3
4
1
0
4
3
1
5
0
1
0
1
0
1
0
1
0
1
9
5
1
2
1
1
4
0
0
0
0
5
0
4
0
0
0
0
0
0
6
4
0