LG MULTI V Service Manual page 140

Hide thumbs Also See for MULTI V:
Table of Contents

Advertisement

Self-diagnosis function
Error
Error Type
No.
Function error of outdoor
151
4way (reversing valve)
n Error diagnosis and countermeasure flow chart
Is 4-Way valve connecter
connection are properly
connected?
Yes
Is 4 Way valve coil
resistance normal?*
Yes
Is 4 way valve coil connected
to 4 way valve normally?**
Yes
In case of more than
2 units, does master outdoor
unit recognize as more
ø
than 2 units? ***
Yes
After reset, can we
check supply voltage at PCB
when starting heating
mode operation****
Yes
Is compressor working
normally?
Yes
After opposite
mode operation to present
mode, is the same error
occurred again?
Yes
Replace 4 way valve*****
Error Point
Function error of 4way
(reversing valve) in Main or
Slave outdoor units
No
Reconnect it
No
Change 4 Way valve coil
No
Re-insert 4 way valve coil
No
Refer to CH 51 & make measure
No
Replace outdoor unit PCB
Check and replace compressor,
No
Magnet switch, corresponding PCB
[refer electric component part]
No
If the same error is occurred in
near future replace 4way valve
- 140 -
Main Reasons
1. Wrong operation of 4way valve because of sludge
etc. inflow
2. No pressure difference because of compressor
fault
3. Wrong installation of In/outdoor common pipe
4. Defect of 4way valve
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents