Error
Error Type
No.
01
Indoor unit air sensor error
02
Indoor unit pipe inlet sensor error
06
Indoor unit pipe outlet sensor error
n Error diagnosis and countermeasure flow chart
Is sensor properly
connected to PCB?
Yes
Is the resistance value
of sensor normal?*
Yes
Change the PCB
** In case the value is more than 100 kΩ (open) or less than 100 Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5 % margin) ➔ Normal
Air temp sensor: 10 °C = 20.7 kΩ : 25 °C= 10 kΩ : 50 °C= 3.4 kΩ
Pipe temp sensor: 10 °C = 10 kΩ
Indoor unit sensor is
No
Connect properly to PCB
No
Change the sensor
: 25 °C= 5 kΩ : 50 °C= 1.8 kΩ
Error Point
1. Indoor unit PCB wrong connection
2. Indoor unit PCB failure
open/short
3. Sensor problem (main reason)
CN-ROOM : Indoor air temp sensor
CN-PIPE IN : Pipe inlet temp sensor
CN-PIPE OUT : Pipe outlet temp sensor
Measure the resistance of outlet pipe temp sensor.
- 103 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Self-diagnosis function
Main Reasons