Cycle Data View - LG MULTI V M ARNU07GTU 4 Series Svc Manual

Table of Contents

Advertisement

Function

4.7 Cycle Data View

This function is intended to identify the Cycle data of ODU, which is running on.
The 7 Segment is display 26 different cycle data.
No
1
Current High Pressure
2
Current Low Pressure
3
Inv. Comp.
4
Fan1
5
Fan2
6
Superheating degreee
7
Subcooling degreee
8
ODU temp.
9
Suction temp.
10
Comp. discharge temp.
12
Liquid pipe temp.
14
SC_OUT
15
Hex
18
Inlet pipe average temp. of IDU
19
Main EEV
21
SC EEV
25
IDU running capacity
26
Total number of IDU
Cycle data view function setting method
Master unit PCB DIP switch on : No.5
Select the mode using
' ', ' '
Push the
button
'●'
Select the Function using
Push the
button
'●'
Selec the Option using
' ', ' '
Push the
button
'●'
Start the Cyce data view fuction : Display the cycle
data value selected from the Segment.
Title
Button : "SVC"
Button : : "Se 7"
' ', ' '
Button : : "op1~op26"
7-seg
Example
Seg_1
P1
4321 kPa
4
P2
1234 kPa
1
H1
120 Hz
H3
110 RPM
H4
110 RPM
T1
53℃
T2
-4.5℃
T3
10℃
T4
43.4℃
T5
150℃
1
T7
10℃
T9
10℃
T10
10℃
T13
-10℃
PLS1
1950 pls
1
PLS3
16 pls
IDU1
24 kBTU
IDU2
10 EA
- 30 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
Seg_2
Seg_3
Seg_4
3
2
1
2
3
4
1
2
0
1
1
0
1
1
0
5
3
0
4
5
1
0
0
4
3
4
5
0
0
1
0
0
1
0
0
1
0
0
1
0
0
9
5
0
1
6
2
4
1
0