Connection To Xec Supercap - Emerson Dixell XEV20D Quick Reference Manual

A bipolar or unipolar motorized driver (stepper) for electronic expansion valves

Advertisement

7.3 CONNECTION TO IPRO
7.4 CONNECTION TO ANALOGUE INPUTS
7.4.1
Temperature probes (NTC and PTC)
2-row sensors that do not require polarity to be respected.
Each sensor must be connected through one of the inputs (from Pb1 to Pb10) and
the common (PbC) as shown in the diagram below.
7.4.2
Pressure transducers and current probes (4 - 20 mA)
2-row sensors that require +12Vdc power supply.
Each sensor must be connected through one of the inputs (from Pb1 to Pb10) and
the power supply (+12V) as shown in the diagram below.
1592025980 XEV20D GB r.2.7 31.07.2019
7.4.3
3-row sensors that require +5Vdc power supply.

8. CONNECTION TO XEC SUPERCAP

The XEC device and the XEV20D driver must be powered by two different
transformers; failure to observe this warning can cause damage to the XEC device or
to the XEV20D driver.
With a connection to the XEV20D driver, to control two electronic expansion valves,
two XEC modules must be used.
For both XEC modules, observe the correct power supply connection sequence
Recommendations:
(connectors 1 of the XEC modules connected to the same pole of the transformer,
- follow the diagram of the
connectors 2 of the XEC modules connected to the other pole of the transformer).
device
used,
for
the
numbering.
-
the
configuration
is
8.1 CONNECTION TO THE XEV20D DRIVER WITH JUST ONE CONNECTED
determined
by
the
VALVE
application.
- if used as a digital input
(potential free - not live),
use the same connection
configuration as of the
sensors.
Recommendations:
- follow the diagram of
the device used, for the
numbering.
- the
configuration
is
determined
by
the
application.
8.2 CONNECTION TO THE XEV20D DRIVER WITH TWO CONNECTED VALVES
XEV20D
Pressure transducers and ratiometric pressure transducers (0 - 5V)
Recommendations:
- follow the diagram of the
device
used,
for
the
numbering.
-
the
configuration
is
determined
by
the
application.