Introduction
June 2021
Other fuels
The detector reacts to other types of fire as follows:
The baseline fire refers to n-heptane 1 ft.
sensitivity.
For fuel fire: standard pan fire size: 1 ft.
For gas flame: 30 in. (0.75 m) high, 10 in. (0.25 m) wide plume fire
Maximum response time: 3 sec.
Table 1-1: Fuel Sensitivity Ranges
Type of fuel
Gasoline
n-heptane
JP5
Kerosene
Diesel fuel
IPA
(1)
LPG
Polypropylene
Hydrogen
Methanol
Methane
Ethanol 95%
Ammonia
Paper
Silane
(1)
30 in. (0.75 m) high, 10 in. (0.25 m) wide plume fire
(2)
20 in. (0.5 m) high, 8 in. (0.2 m) wide plume fire
1.5.2
Cone of vision
Horizontal: 100 °
16
(1)
1
(2)
(2)
2
2
(0.1 m
) and is defined as 100 percent
2
2
(0.1 m
)
Max. distance (ft. / m)
66 / 20
66 / 20
50 / 15
50 / 15
50 / 15
43 / 13
43 / 13
43 / 13
37 / 11
26 / 8
26 / 8
25 / 7.5
20 / 6
16 / 5
6 / 1.8
Reference Manual
00809-0100-4977
Emerson.com/Rosemount