Introduction
June 2021
The accessories: tilt mount (PN 00975-9000-0001), weather cover (PN 00975-9000-0003
[plastic] and PN 00975-9000-0004 [stainless steel]), duct mount (PN 00975-9000-0002),
and air shield (PN 00975-9000-0005), are included in the approval.
This product is available to use in hazardous zones 1 and 2 with IIC gas group vapors
present and zones 21 and 22 with IIIC dust type present.
FM
The flame detector is certified to FM explosion proof and functionality per FM3260.
•
Class I, Division 1, Groups B, C, and D, T5 Ta = 85 °C.
•
Dust ignition proof - Class II/III Division 1, Groups E, F, and G.
•
Ingress protection - IP67, IP66, NEMA 250 Type 6P
•
For more details, see FM Report Project ID3029553.
SIL-2 (TÜV)
The flame detector is certified to SIL-2 requirement per IEC 61508A, Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
•
Alert signal via 0-20 mA current loop
or
•
Alert signal via alarm relay and fault relay
For more details, see
EN54-10
The flame detector is approved per EN54-10 and CPD.
•
The detector has been tested and approved per EN54-10 by Vds (Germany).
•
This test includes functional test, environmental test, EMI/EMC test, and software
check.
•
For more details, see Test Report BMA 13109.
InMetro (UL)
The flame detector is in compliance with the following standards as of May 18, 2010:
•
ABNT NBR IEC 60079-0
•
ABNT NBRIEC 60079-1
•
ABNT NBR IEC 60079-7
•
ABNT NBR IEC 60079-18
•
ABNT NBR IEC 60079-31
•
INMETRO decree No. 179
For further details, see the Certificate of Compliance No. UL-BR 16.065XX.
14
TUV Report No. 968/FSP
1223.
Emerson.com/Rosemount
Reference Manual
00809-0100-4977