Combustion Test Target Ranges
The Low Fire (Zero-offset) valve adjustment 
cap on the gas valve has been factory set. 
Do not tamper with or adjust this screw in the 
field. Contact the factory for written 
instructions if considering field adjustment of 
the Low Fire (zero offset) adjustment.
The High Fire (Gas:Air) ratio adjustment 
screw is a slotted brass screw to the left of 
the long brass protrusion on the front of the 
gas valve. It will have to be adjusted to attain 
optimum combustion results whenever fuel 
conversion is undertaken; however, no 
mixture adjustment must be performed 
unless done by a qualified technician using 
properly functioning and calibrated 
combustion analyzing equipment.
Fuel
Range
Natural Gas 
9.0 – 10.0
Propane 
10.3 – 11.3
Table 1
Combustion test target ranges - CO
Note: Low Fire CO 2  should be at least 0.5% lower than High Fire CO 2 .
2 |
 
Figure 1 Gas valve and fan
High Fire
Target
9.5
8.2 – 9.2
10.8
9.3 – 10.3
/ Maximum CO
2
Low Fire
Range
Target
8.7
9.8
Co Max PPM
< 150
< 250