Eaton VCP-W Instructions For Installation, Operation And Maintenance page 13

Vacuum circuit breakers
Hide thumbs Also See for VCP-W:
Table of Contents

Advertisement

1B131006EN
Table 1.9 (ANSI Standards) Type VCP-WXC Circuit Breaker Through 15 kV Rated Symmetrical Current
(Standard Ratings)
See Page 40 (Figure 5-5A) for Control Schemes and Diagram that apply to this breaker. This Breaker differs from
The Standard Breaker with the addition of a third motor cut-off switch and addition of two wires.
Identification
Rated voltage
Circuit
Voltage
Insulation level
Breaker
Max
Voltage
Withstand test
Type
Voltage
Range
factor
Power
Frequency
(1 Min.)
V
K
KV rms
kV rms kV Peak
150 VCP-WXC 63
17.5
1
42
E f f ec t iv e 0 7/ 2 0 1 7
Courtesy of NationalSwitchgear.com
Short Circuit Current
Sym.
% dc
Asym.
Lightening
Continuous
Inter-
compo-
Inter-
Impulse
Current at
rupting
nent
rupting
1.2x50us
60 Hz
at V (Isc)
(Idc)
(It)
kA rms
A rms
%
kA rms kA Peak kA rms
Total
1200
61
83
95
2000
63
61
83
3000
61
83
Transient
Inter-
Maximum
Recovery
rupting
Permissible
Closing
Short-
Voltage
Time
Tripping
&
Time
(RRRV)
Delay
Latching
Current
(1)
Capa-
for
(3)
bility
3 sec.
Ms
Seconds
kV / µs
1.07
175
63
50
2
1.07
1.07
Basis
Capacitor Switching Ratings
General
Definite Purpose
Purpose
Isolated
Back to Back Capacitor Switching
Shunt
Capacitor
Capacitor
Inrush
Inrush
Bank
Bank
Current
Frequency
Current
Current
A rms
A rms
kA Peak
kHz
200,1600(9)
7.7
465
200,1600(9)
7.7
465
200,1600(9)
7.7
465
P a g e 7
Mechanical
Endurance
No-load
Operations
10,000
10,000
10,000