Connections for control valve actuator, 0–10 V
Accessory
Designation
Description
Valve
When making connections, pay attention to the valve's control direction. To invert
the valve's control direction, either change the position of DIP switch 6 or invert the
direction from settings.
Inverted control disabled, DIP switch 6 ON
Signal
Increases
Decreases
Inverted setting enabled, DIP switch 6 ON
Signal
Increases
Decreases
Inverted control disabled, DIP switch 6 OFF
Signal
Increases
Decreases
Inverted control enabled, DIP switch 6 OFF
Signal
Increases
Decreases

3.6 Heating circuit pump

The connections for the heating circuit pump are indicated in the unit's electric diagram.
The location of the pump is indicated in the piping diagram.
Enable the pump from Initial setup settings (see chapter Commissioning) or from
Heating settings (see the table below). If valve control is enabled, the pump will also
be enabled automatically.
28 (54)
Heating circuit control valve actuator, 0–10 V 24 V
36962220
Esbe ARA639 12520100 (12520117 OEM), 0–10 V, 4–20 mA, 24 V AC/DC, 3 wires,
15/30/60/120 s 90°, pre-set to 60 s (DIP switch 2 ON), pre-set to OPEN (with
increasing signal) counterclockwise CCW (DIP switch 6 ON)
34034065, 34034067, 34034068, 34034467
Control direction
Open (more heat)
Closed (less heat)
Control direction
Closed (less heat)
Open (more heat)
Control direction
Open (more heat)
Closed (less heat)
Control direction
Closed (less heat)
Open (more heat)
Rotation direction
Counterclockwise (CCW)
Clockwise (CW)
Rotation direction
Counterclockwise (CCW)
Clockwise (CW)
Rotation direction
Clockwise (CW)
Counterclockwise (CCW)
Rotation direction
Clockwise (CW)
Counterclockwise (CCW)
0 V closed,
10 V open
0 V open, 10
V closed
0 V closed,
10 V open
0 V open, 10
V closed
M8006 2123EN