1.4 Transportation and storage

Storage
Store the unit upright in a warm, dry place. Protect the device against water and dust.
Do not stack goods on the unit.
Transportation
Transport the unit upright and protected against water and dust. Do not stack goods
on the unit. Use only safe lifting and handling methods when moving or lifting the
unit. After lifting, lower the unit carefully down onto the floor. Hard impacts can cause
equipment damage.
When lifting the unit, grab the unit by the frame. Do not lift the heat pump from the
bottom of the compressor unit.
● The unit's exterior panels may be removed to make it easier to carry and move the
unit.
● The unit can be carried short distances by the side bars.
● If necessary, the compressor unit can be detached from the frame of the heat pump
before carrying or tilting the unit.*
● Do not lift or move the unit with the domestic hot water tank filled.*
*Applicable to heat pumps with an integrated DHW tank.
The compressor unit can be tilted up to 45 degrees from horizontal. If you need to tilt
the heat pump beyond 45 degrees, remove the compressor unit.
● If the unit is tilted beyond 45 degrees, the compressor may not receive proper
lubrication at startup. As a result, the compressor may become damaged.
● If the unit has been accidentally tilted beyond 45 degrees, leave the unit in vertical
position for at least three hours before starting the compressor.
M8006 2123EN