Installation
Terminal Block Assignment Status Indicator
Normal Operation
Terminal
Description
1 - 2
24 VDC power supply; terminal 1 to +24 VDC and
terminal 2 is 0V
3 - 4
RESET button; normally open switch contact
(N.O.)
4 - 5
TEST button; connect a normally closed (N.C.).
8
Input of the muting B sensor. N.O. contact of the
muting sensor (photocell, proximity switch, others).
9
Input of the muting A sensor. N.O. contact of the
muting sensor (photocell, proximity switch, others).
10
Input of the muting D sensor. N.O. contact of the
muting sensor (photocell, proximity switch, others).
11
Input of the muting C sensor. N.O. contact of the
muting sensor (photocell, proximity switch, others).
12
Not used.
13 -14
(OUT1) safety output 1 with N.O. contact.
15 - 16
(OUT2) safety output 2 with N.O. contact.
17 - 18
Power supply for the transmitter (TX1) for
Light Curtain 1.
Terminal 17 > +24 VDC; terminal 18 > 0V.
19 - 20
Not used.
21- 22
Power supply for the transmitter (TX2) for
Light Curtain 2.
Terminal 21 > +24 VDC; terminal 22 > 0V.
23 - 24
Not used.
25 - 26
Power supply for the receiver (RX1) for
Light Curtain 1.
Terminal 25 > +24 VDC; terminal 26 > 0V.
27 - 28
Connect to the PNP outputs of the receivers (RX1)
of the Light Curtain
Control output 1 wire and control output 2 wire to
terminal 27 and 28.
(Both control outputs must be used.)
If Light Curtain1 is not used, connect terminal 27
and 28 to terminal 25.
29 - 30
Power supply for the receiver for (RX2) for
Light Curtain 2.
Terminal 29 > +24 VDC, terminal 30 > 0V
31 - 32
Connect to the PNP output of the receivers (RX2)
of Light Curtain 2.
Control output 1 wire and control output 2 wire to
terminal 31 and 32.
(Both control outputs must be used.)
If Light Curtain 2 is not used, connect terminal 31
and 32 to terminal 29.
Dimensions
F3SP-U2P
Dip Switch Settings
No.
ON/OFF
Function
1
X
Not Used
2
OFF
Muting A-B acts on light
curtain 1;
Muting C-D acts on light
curtain 2
ON
Forbidden
3
OFF
Muting - 60 seconds
ON
Muting - infinity
4
OFF
Manual reset mode
ON
Auto reset mode
Status Indicator
Normal Operation Installation
Code
Description
H
Initial test is activated.
8 to 1
Countdown during the initial test.
U
Test button is pressed. Output contacts are opened.
Override function is activated.
A
Normal cycle: output contacts are closed
E
Light curtain is interrupted in automatic mode: output
contacts are opened.
F
Interlocked condition: output contacts are opened.
Error Indication
Code
Description
7
Error of muting lamp.
8
Irreversible system error or error on the output contacts.
9
Wrong muting sequence request.
7
F3SP-U2P
Comment
--
(default
setting)
--
--
(default
setting)
--
(default
setting)