THROUGH THE WALL UNIT

2.2.7 SLEEP MODE

2.2.7.1 Sleep mode will only function under heating, cooling, and auto heat/cool modes.
2.2.7.2 In cooling mode, at the beginning of sleep function, if room temperature> setting
temperature, the compressor and outdoor fan will start normally. Indoor fan motor will run in
low speed. The four-way valve will be closed. If room temperature≤ setting temperature, the
unit will start sleep mode. Fan speed will be set at low speed. Air flow direction can be
adjusted or stay in one position.
2.2.7.3 In heating mode, at the beginning of sleep function, if room temperature < setting
temperature, the compressor, outdoor fan and four-way valve will start normally. Indoor fan
motor will run in low speed. If room temperature ≥ setting temperature, the unit will start sleep
mode. Fan speed will be set at low speed. Air flow direction can be adjusted or stay in one
position.
NOTE: When Timer and Sleeping function are set at the same time, the unit will work with
Timer function