Interrupts - Siemens SIMATIC ET 200SP Manual

Analog input module ai 2xu/i 2-/4-wire hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

6.2

Interrupts

The I/O module supports diagnostic and hardware interrupts.
Diagnostics interrupts
The module generates a diagnostic interrupt at the following events:
• Short-circuit (current: sensor supply; voltage: 1 to 5 V, encoder supply)
• Wire break (current: 4 to 20 mA)
• High limit violated
• Low limit violated
• Error
• Parameter assignment error
• Hardware interrupt lost
• Supply voltage missing
• Channel temporarily unavailable
Hardware interrupts
The module generates a hardware interrupt at the following events:
• Violation of low limit 1
• Violation of high limit 1
• Violation of low limit 2
• Violation of high limit 2
S7-1500
Detailed information on the event is available in the STEP 7 online help.
The block interface is represented here with optimized block access, which is set in the TIA
Portal by default.
Name
Data type
LADDR
HW_IO
USI
WORD
IChannel
USInt
EventType
Byte
Analog input module AI 2xU/I 2-/4-wire HF (6ES7134-6HB00-0CA1)
Equipment Manual, 05/21, A5E51055079-AA
Comment
Hardware identifier of the module triggering the interrupt
USI (High/Low)
Channel that triggered the hardware interrupt
Error event
Interrupts/diagnostics alarms
6.2 Interrupts